RESTRAINT CHARACTERISTICS
At high current levels, the inevitable difference in the
saturation characteristics between current transform
ers requires a compensating decrease in relay
sensitivity. The design of the BE1-87G provides a
restraint factor that is proportional to input current.
Specifically, the BE1-87G compares the two sensed
currents (in and out) to determine which is less. This
lower current level becomes the restraining current.
The difference between the two sensed currents (I0
) is compared to a reference established by the sensitivity
setting and adjusted by an amount proportional to the
restraining current. (The typical ratio is given in the
formula on page 3.) This makes the BE1-87G more
sensitive to low current internal faults, for which the
relay should operate, and less sensitive to external
faults with high levels of through current for which the
relay should not operate.