PUSH-TO-ENERGIZE OUTPUTS

A push-to-energize pushbutton is included for each tripping output contact. These pushbuttons can be

used to verify correct operation of external control circuit wiring without the need to supply test signals to

the relay. Control power must be applied for this function to operate. The pushbuttons are recessed

behind the relay front panel and are not accessible with the cover installed.

TARGETS

One target is included for each tripping function as specified by style number. Targets are operated either

by the internal signal initiating tripping (internally operated) or by a minimum of 200 mAdc flowing through

the series circuit consisting of the target coil and output relay contacts (current operated). Within a

specific relay, all targets must be operated in the same way.

POWER SUPPLY OPTIONS

Various power supply options are available to allow the BE1-67N relay to be used with standard supply

voltages. See the style chart for details.

POWER-UP DELAY

A power-up delay timer is initiated upon application of control power to the relay to prevent undesired

contact transitions when sensing signals are present. Operation of measuring circuits and output circuits

are inhibited (less than 0.5 seconds) until the power-up delay period has expired.