Principles of Symmetrical Components
Principles of symmetrical components allow an unbalanced system to be
considered as three separate, balanced subsystems. These balanced
subsystems may then be analyzed as single phase quantities.
These quantities are the positive, negative, and zero sequence components
of current and voltage.
The positive sequence component of current (I1) represents the portion of
the total current which has normal phase rotation and produces no adverse
effect on the system. An ideally balanced system contains only positive
sequence phase currents and voltages.
The zero sequence component of current (I0) also has no adverse effect
on a three-phase, three-wire (no neutral connection) power system because
it produces no appreciable magnetic flux and causes no excessive heating
in the generator rotor or windings.
The negative sequence component of current (I2) produces a magnetic flux
in the stator that has the same rotational speed as the rotor flux, but in the
opposite direction. This causes the stator magnetic flux to rotate at twice
the system frequency and induce eddy currents into the rotor. These eddy
currents create excessive heat in the rotor iron and windings, and, if allowed
to persist, could result in severe damage to the system.