Application – Standard Models
Breaker Failure
BE1-BPR relays are intended to provide a preprogrammed solution for most
breaker failure relaying applications. Breaker failure relaying is the use of a
current monitoring relay to determine whether or not current continues to
flow into a faulted circuit after a breaker has been instructed to interrupt the
circuit. If current continues to flow into the faulted circuit after a defined
period of time has elapsed (sufficient for the breaker to have interrupted the
current), the circuit breaker is considered to have failed. Steps must then be
taken to trip the next set of breakers in the power system to prevent system
damage. Breaker failure schemes must be designed to isolate both the faulted
circuit and the failed breaker.
Several reasons why a breaker fails to clear a fault are:
• Trip circuit is open (broken wire, blown fuse, open trip coil).
• Interrupting mechanism stuck, leaving a single phase of a three-phase circuit
connected.
• Interrupter flash-over due to the loss of dielectric strength through
contamination or damage.
• Operating mechanism failed to operate.