Breaker failure relays detect these conditions and initiate backup procedures.
Breaker failure relays are applied on a per breaker basis. That is, one breaker
failure relay for each breaker in the substation. BE1-BPR relay outputs must be
arranged to initiate the tripping of all the circuit breakers necessary to isolate
the fault if the protected circuit breaker fails to operate. The relay may also
need to initiate transfer tripping of remote breakers to accomplish this task.
Transfer tripping of the remote line end for a breaker failure should also block
reclosing of the remote circuit breakers. External lockout relays are typically
used to trip and block reclosing of the backup breakers because they normally
require a positive operator action to reset them.
Typically, breaker failure protection is applied to transmission and sub-transmission
systems. However, breaker failure protection may be applied to any portion of the
power system where failure of a circuit breaker to operate properly could result in
severe system damage or instability. Breaker failure protection can also be used to
selectively clear a failed breaker in a station with multiple buses without clearing
the entire station.