FUNCTIONAL DESCRIPTION
Frequency Compensation
The frequency compensation characteristic of Figure 1 is
used to improve system load pickup performance by
restraining voltage recovery until frequency has also
started to recover. The regulator is shipped from the
factory set at a 47-Hz corner frequency for 50 Hz systems.
For 60 Hz systems, a 57-Hz corner frequency is achieved
by moving the jumper wire from the 50 and HZ terminals
to the 60 and HZ terminals.
This feature is designed to protect the generator and
regulator by allowing disconnection of the overloaded
part(s) of the system. Should the regulator be allowed to
run in excess of its rated current for any extended period
of time after the protection output closes, failure of the
recommended supply fuse will occur, but regulator
damage may also take place.