Flexible Configurations – Up to 600Vac/600 Amp/200kA SCCR,
or 125Vdc/600 Amp/100kA SCCR. 125Vdc rating applicable on
MLO panels only, up to 80A.
• 30. 60. 100. 200. 225. 400 and 600 A main ratings
• 125 Vdc rating ideal for utility and petro-chem control circuits or UPS
circuits
• 1 to 100 A fuse ratings to closely match loads
• Available in fused or non-fused main disconnect switch, or MLO (Main
Lug Only) configurations with a choice of 18. 30. 42. 60. 72 and 84 branch
positions, up to 200 A, in NEMA 1 or 3R enclosures to easily meet branch
or service panel installation needs
• Feed through lugs or fused loadside disconnect available
• Same size footprint as traditional circuit breaker panelboards
• 20” W x 5” D x various heights (depending on configuration), See data
sheet for specific dimensions/configurations
Addresses NEC® Selective Coordination Requirements
• This cULus Listed panelboard makes it easy to provide systems that
comply with NEC® Selective Coordination Requirements for Emergency,
Legally Required Standby, Healthcare Essential Electrical and Critical
Operation Power Systems (COPS) per 700.27. 701.18. 517.26 and 708.54
• Full fuse-system selective coordination is easy from source to branch.
Just follow published fuse selective coordination ratios – no need for
plotting time-current curves or expensive studies