OVERVIEW
The F892 redundant fieldbus power supply is designed to provide redundant power
for eight (8) Foundation fieldbusTM H1 segments. Pluggable connectors are provided
on the F892-CA module carrier for connection to the eight segments. Fixed screw
terminals are used for the 8 Host segment connections. Power for the eight fieldbus
segments is provided by two F801 or F802 Power Modules mounted to the carrier
and operating in a redundant configuration. Failure alarms, galvanic isolation, power
conditioning and segment termination are incorporated into each Power Module. A
single F801 or F802 module may be used where redundancy is not required.
Each Power Module has indicator LEDs to show both its status and that of the eight
segments under power. In normal operation, each green ‘Segment’ LED is lit, showing
that the segment is powered. If a segment is shorted, or its voltage is below the rated
output, its LED is extinguished, and the red ‘Alarm’ LED is lit. Redundant 24V DC (nom.)
input power is connected to the F892-CA carrier using two-part pluggable connectors.
Field wiring connections are available with either pluggable screw terminals (F892-PS)
or pluggable spring clamp terminals (F892-PC).