INSTALLATION
BE3 temperature relays are designed for mounting on
standard DIN rails that comply with DIN-EN 50022.
Mounting involves hooking the top edge of the cutout on the
base of the case over one edge of the DIN rail. The opposite
side of the cutout containing the release clip is then pushed
over the opposite side of the DIN rail. To remove or
reposition the relay, lever the release clip and move the
relay as required. BE3 relays should be installed in a dry,
vibration-free location where the ambient temperature does
not exceed the operating temperature range. Connections to
the relay should be made using wire that meets applicable
codes and is properly sized for the application. Figure 2
illustrates the terminal connections for the BE3-49R
temperature relay.
A burden resistor must be installed across all unused RTD
inputs that are not connected to an actual RTD. For units
with style number 5HXXX, it is suggested that a 10 Ω
resistor be connected across any unused RTD inputs. For
units with style number 5IXXX, it is suggested that a 100 Ω
resistor be connected across any unused RTD inputs. The
minimum power rating for the burden resistors is ¼ W.