The BE1-CDS240 is available in a fully draw-out MX case with configurations for horizontal 19″ rack
mounting, horizontal panel mounting and vertical panel mounting. BE1-CDS240 features include:
• Up to four restraint inputs (four three-phase current circuits) and two virtual current circuits that
can be used with any combination of two current inputs
• Independent ground input
• Three voltage inputs (Va, Vb, Vc, to Vn)
• Three-phase percentage differential protection with harmonic restraint
• Three-phase voltage, frequency and overcurrent protection
• Four setting groups
• One embedded preprogrammed logic scheme
• Fourteen or 10 programmable outputs
• Eight or 12 contact sensing inputs
• Breaker failure protection for four breakers
• Front panel HMI (human-machine interface)
• Communications ports: one front RS-232, one rear RS-232, one rear RS-485 and one rear
IRIG port
• Communications protocols available: DNP3, Modbus® RTU, and ASCII
• Sequence of events recording
• Fault recording
• Oscillography
• Demand reporting
• Differential current monitoring
• Optional load profile reporting