BE3-27T and BE3-59T ac voltage relays have two external, user
adjustable controls marked SET and DELAY. The BE3-27T/59T has
four controls: UNDER SET, OVER SET, UNDER DELAY, and
OVER DELAY. The SET control adjusts the relay trip point. An
overvoltage trip causes the relay output to energize when the
voltage rises above the SET threshold. The overvoltage SET level
is adjustable from 100 to 125% (±3%) of nominal input (Vnom
). An
undervoltage trip causes the relay output to de-energize when the
voltage decreases below the SET threshold. The undervoltage SET
level is adjustable from 75 to 100% (±3%) of nominal input. Time
delay is the amount of time that elapses after the trip point is
reached and when the output relay operates.
Setting Example: a BE3-59T relay with a nominal input rating of 240
Vac has the following settings:
• SET – 120%
• DELAY – 4 seconds
A trip occurs when the sensing voltage rises above 288 Vac and 4
seconds elapses. Reset occurs when the voltage decreases below
285.6 Vac (1% of nominal below setpoint).