The measuring ranges generally reach accuracy class 0.01%. For further
information please refer to the documentation. Through the feature
“ExtendedRange” the user has the full technical measuring range available,
up to 107% of the specified nominal measuring range, depending on the
measuring range. This feature can be disabled, in order to ensure
compatibility with the “LegacyRange” of the EL30xx/EL31xx series.
To suppress aliasing effects, the input channel features two configurable
numeric software filters up to 39th order FIR/6th order IIR.
The filters can be preselected or freely described, so that a band stop or
a band pass can be realized. The measurement at the differential input
channel is digitized with a resolution of 24 bit and 10 ksps and is
transmitted to the higher-level automation device electrically isolated and
optionally with oversampling. The data rate can be internally reduced,
in which case the filters have to be adjusted accordingly.
Non-linear characteristic sensor curves can be corrected flexibly through
an integrated sampling points table. Simple mathematical operations are
also possible.
Leave a comment