THEORY OF OPERATION
Rectifier diodes mounted on the rotor of a brushless generator or motor
fail by either opening or shorting. If a rectifier shorts, very high current
flows through the associated exciter armature winding and causes
excessive heating and probable failure of the exciter.
If a rectifier opens, the voltage regulator will substantially increase the
excitation to maintain the operating level. This constant, high level of
excitation could lead to failure of the regulator.
The EDM-200 determines the status of the rotating rectifiers by sensing
the ripple content of the exciter field current. The waveform shown in
Figure 2A is the normal ripple measured with all diodes functional.
Figure 2B illustrates a waveform where one diode is open. Figure 2C
illustrates a waveform where one diode is shorted.
Automatic Gain Controlled Amplifier
As the output of the input amplifier varies from 1 to 4 volts, the associated
ripple content also varies. To prevent the monitoring circuits from
interpreting the 1 to 4 volt change as a diode failure, the automatic gain
controlled amplifier offsets the signal variations so that the monitoring
circuit monitors the ripple in a constant amplitude signal.