Options
The AVC63-12 and AVC125-10 may be equipped with the following options to
enhance operation.
Remote Voltage Adjust
Connect a 10 kΩ, 2 W potentiometer across terminals 6a and 7. remove the
jumper from terminals 4 and 7. and adjust the front panel VLT ADJ control fully
clockwise to enable remote adjustment of the voltage setpoint.
Inrush Current Reduction Module
A Basler ICRM-15 is required when energizing the AVC63-12 or AVC125-10 from
a source that is already at the regulator input power rating.
The ICRM-15 minimizes the amount of inrush current that could be seen when
power is applied.
Excitation Disable
This option disables excitation by removing power from the regulator. A switch
removing voltage from terminals 26. 28 and/or 30 will remove regulator power.
Excitation Limiter
The Basler EL 200 provides an initial, fast-acting limit of the field current at a
user-defined level. Once the field current has changed to the selected level, the
EL 200 provides a signal to the regulator to change the excitation level.