MOUNTING
The EDM-200 should be mounted in a position that enables easy viewing of
the bar graph display. Figure 4 illustrates the overall dimensions and mounting
hole locations of the EDM-200.
CONNECTIONS
Depending upon the application, the EDM-200 should be connected according
to the connection drawing shown in Figure 5 or Figure 6. All EDM-200
connections are terminated with #6 screws which have a maximum torque
rating of 9 inch-pounds (1 N•m).
AVR Ripple Amplifier
Since the AVR output consists of pulses, a strong ripple component
consisting of these pulses is present in the field current and makes the
detection of an open diode difficult. To eliminate the AVR ripple, the
AVR voltage at terminal F+ is passed through a filter, a null adjustment,
and the AVR ripple amplifier. The amplifier output is then used by the
input amplifier to cancel out the AVR ripple component in the field current.