INTRODUCTION
BE3 ac current relays provide current monitoring and protection in
both single-phase and three-phase systems. They are used in
applications such as motor protection, load detection, and generator
control. Undercurrent, overcurrent, and combined over/undercurrent
units are available. BE3 ac current relays operate when the
adjustable trip point is reached. A time delay control is provided with
an adjustment of 0 to 10 seconds (relay operating time is typically
200 milliseconds). This time delay may be used to prevent false
tripping when there are slight variations in the sensed current.
On overcurrent units, the output relay energizes when the input
signal exceeds the trip point. On undercurrent units, the output relay
de energizes when the input signal goes below the trip point. A red
LED indicates the state of the output relay. A green LED indicates
the condition of the power supply.