Mounting Hardware
The AVC Sensing Module can be mounted directly on a genset using #10-32 or
equivalent hardware. A lock washer should be used between the screw head and
body of the module. Torque applied when tightening the mounting hardware
should not exceed 25 inch-pounds (2.8 N•m).
CONNECTIONS
All AVC Sensing Module connections are located on the back panel. Sensing voltage
is applied to the lower, six position terminal block. Sensing voltage is supplied to the
voltage regulator from the upper, three-position terminal block. Connections consist
of #6 terminal screws. Each terminal accepts a maximum wire size of 12 AWG (13
mm2). When securing connections, apply no more than 9 in-lb (1 N•m) of torque to
each terminal screw.
Before connecting the module, review the terminal descriptions listed in Table 1 and
the connection diagram of Figure 2. At any given time, only one of the two sets of
sensing voltage input terminals can be used. Under no circumstance can both the
480 Vac and 600 Vac sensing input terminals be connected to a voltage source.
MAINTENANCE
A periodic inspection of the AVC Sensing Module should be made to ensure that all
connections are clean and tight.
The AVC Sensing Module contains no serviceable parts. If a failure occurs, replacement
of the module is recommended.