• Terminals are brass studs No. 10–32 with one lockwasher,

flatwasher, and regular nut

• The core and coil assembly is encased in a thermoplastic

shell and filled with resin

• It is desirable to use a 1.6 amp fuse in the primary of the

M‑0362 to protect the source transformer

• A circle diagram for the estimation of the errors for other

than rated burdens is provided

• Each transformer includes two plastic terminal covers

• Approximate weight: 7.75 lbs

Specifications

Frequency: 60 Hz

Input Voltage: 120 V

Standard Secondary Voltage: 120 Volts

Insulation Level: 0.6 kV, BIL 10 kV full wave

Accuracy Class: 0.6 W, 1.2 x at 60 Hz

Thermal Rating:

150 VA at 30° amb

100 VA at 55° amb

M‑0362 Voltage Transformer is manufactured to meet the requirements

of ANSI C57.13. Classified by U.L. in accordance with IEC 185.

Patent and Warranty

M‑0362 is covered by U.S. Patents, and carries a five year warranty from

date of purchase.