Automatic Transfer: The digital Motor Bus Transfer System (MBTS)
provides the following Automatic Transfer logic and features:
• Transfer initiated by protective relay external to the MBTS
• Automatic Transfer after a loss of the motor bus supply voltage
based on the programmable undervoltage element. This provides a
selectable backup feature if a protective relay transfer is not initiated.
• Fast Transfer with adjustable phase angle limit, delta voltage limit
and delta frequency limit
• In-Phase Transfer at the first phase coincidence if Fast Transfer is
not possible.
• Residual Voltage Transfer at an adjustable low residual voltage limit
if Fast Transfer is not possible
• Fixed Time Transfer after an adjustable time delay
• Programmable load shedding prior to initiating In‑Phase Residual
Voltage Transfer and Fixed Time Transfer
• Verify the new source (the source to which the bus is being
transferred) is healthy and within acceptable upper and lower voltage
limits