Sensitivity Control
Sensitivity adjustment prevents LTC transformers from hunting or being several
steps apart.
Sensitivity is adjustable from two times normal to 0.5 times normal in nine steps.
Parallel/Independent Switch
Mode of LTC control is switch selectable.
Transient Protection
Input and output circuits are protected against system transients. The M‑0115A
will exhibit no component failure or false commands when subjected to the
requirements of ANSI/IEEE C37.90.1-1989. which defines oscillatory and fast
transient surge withstand capability. All inputs and outputs will withstand 1500
Vac to chassis or instrument ground for one minute. Voltage inputs are electrically
isolated from each other, from other circuits, and from ground.
Mounting
Panel mounted using 8‑1/2″ x 6‑1/8″ cutout (21.59 cm x 15.56 cm). May be
surface mounted using the M‑0124 Surface Mounting Adapter.
Application
This manual includes an overview of typical system setup and connections, necessary
components, and the information necessary to implement a paralleling scheme using
the M‑0115A in the Circulating Current paralleling method.