Provides all components that are required for paralleling LTC Transformers
using the Circulating Current Method
The M‑0115A Parallel Balancing Module includes all the components that
must be added to load tapchanging (LTC) transformers to permit them to
operate in parallel, using the circulating current method. The transformer
controls must have a 0.2 A input for load and circulating current. Through
the use of a circulating current sensitivity adjustment, the M‑0115A avoids
the problems of hunting (caused by too much sensitivity), or permitting
the transformers to be several steps apart (caused by too little sensitivity).
The M‑0115A conforms to the procedure described in ANSI C57.12.10‑1988.
paragraph 10.2.
Current Inputs
Rated at 0.2 A, 12 VA, 50/60 Hz.
Current Ratings
Either winding K1. K2 or ACT from terminal TB1‑1 to TB1‑5 is rated for 0.2 A
continuous.
All windings will withstand the following: 0.4 A continuous, 2.9 A for 5 sec;
3.3 A for 4 sec; 4.0 A for 3 sec;
5.0 A for 2 sec.
Cores are unsaturated at 12 VA burden.