Line Current, used for Line Drop Compensation, is provided by an Auxiliary
Current Transformer. The current transformer drops the line current to a
0.2 A full scale rating. The M 0121 or M 0169A can be used for CTs with
a 5 A secondary. The M 0169A can be used for CTs with either a 5 A or
8.66 A secondary.
Input
M‑0121: Nominal 5 A current transformer circuit.
M‑0169A: Nominal 5 A or 8.66 A current transformer circuit.
Output
Nominal 0.2 A ±5%, linear to 0.4 A.
Output Rating
M‑0121: (into M‑0067 terminals 3 to 4 or 5 to 6) 0.1 VA, 0.2 A current.
M‑0169A: 5 VA, 0.2 A current.
HI POT: 1500 Vac rms. Primary to secondary and either to case.
Mounting Dimensions
M‑0121: 5″ x 2‑1/8″ (12.7 cm x 5.1 cm), 4 holes, 7/32″ (0.6 cm) diameter.
M‑0169A: 5‑5/8″ x 3″ (14.3 cm x 7.6 cm), 4 holes, 7/32″ (0.6 cm) diameter.
Compliance
cULus‑Listed per 508 – NMTR.E155037 Industrial Control Equipment
– NMTR7.E155037 Industrial Control Equipment Certified for Canada
CAN/USA C22.2 No. 14‑M91