Line Current, used for Line Drop Compensation, is provided by an Auxiliary

Current Transformer. The current transformer drops the line current to a

0.2 A full scale rating. The M 0121 or M 0169A can be used for CTs with

a 5 A secondary. The M 0169A can be used for CTs with either a 5 A or

8.66 A secondary.

Input

M‑0121: Nominal 5 A current transformer circuit.

M‑0169A: Nominal 5 A or 8.66 A current transformer circuit.

Output

Nominal 0.2 A ±5%, linear to 0.4 A.

Output Rating

M‑0121: (into M‑0067 terminals 3 to 4 or 5 to 6) 0.1 VA, 0.2 A current.

M‑0169A: 5 VA, 0.2 A current.

HI POT: 1500 Vac rms. Primary to secondary and either to case.

Mounting Dimensions

M‑0121: 5″ x 2‑1/8″ (12.7 cm x 5.1 cm), 4 holes, 7/32″ (0.6 cm) diameter.

M‑0169A: 5‑5/8″ x 3″ (14.3 cm x 7.6 cm), 4 holes, 7/32″ (0.6 cm) diameter.

Compliance

cULus‑Listed per 508 – NMTR.E155037 Industrial Control Equipment

– NMTR7.E155037 Industrial Control Equipment Certified for Canada

CAN/USA C22.2 No. 14‑M91