Basler Electric FGD-2 is typically preinstalled in an excitation control system
Installation
The FGD-2 is typically preinstalled in an excitation control system.
If replacement is necessary, carefully label and document each of the
connections to the FGD-2 in order to properly reconnect the new module.
FGD-2 connectors and indicators are illustrated in Figure 1. Locator
letters in Figure 1 correspond to the lettered descriptions in Table 1.
When a replacement FGD-2 is installed in a DECS-2100 or ECS2100
system, the system calibration values may need to be updated.
Retrofitting an FGD
Although the FGD-2 is smaller in size than the FGD, it may still be mounted
in place of an FGD using only four of the six existing mounting holes.
Either the upper four or the lower four mounting holes may be used.
BE1-FLEX
The FGD-2 output can be connected to any analog input of the BE1-FLEX.
Field ground protection settings can be configured in BESTCOMSPlus.
Ground Detection Source
The ground detection source supplies approximately –60 Vdc to the positive
side of a machine field and measures the level of leakage current to ground.
The positive side of the field bus is held negative with respect to ground.