Welcome to the official website of CNIACS Automation Technology Co., Ltd!

Woodward Digital Synchronizer and Load Control (DSLC) SPECIFICATIONS

SPECIFICATIONS

EENNVVIIRROONNMMEENNTTAALL

SSPPEECCIIFFIICCAATTIIOONNSS

Operating Temperature…………………………………………-40 to +70 °C (-40 to +158°F)

Storage Temperature…………………………………………….-55 to +105 °C (-67 to +221°F)

Humidity………………………………………………………………95% at 38 °C

Electromagnetic Susceptibility………………………………..ANSI/IEEE C37.90.2; ANSI C37.90.1-1989

Mechanical Shock………………………………………………..US MIL-STD 810C, Method 516.2. Procedures I, II, V

Vibration………………………………………………………………US MIL-STD 167. Type I

EELLEECCTTRRIICCAALL

SSPPEECCIIFFIICCAATTIIOONNSS

CCoonnttrrooll

PPoowweerr

SSuuppppllyy

IInnppuutt

Operating…………………………………………………………….8–32 Vdc continuous (as low as 10 Vdc, 1.8 A max, or as high

as 77 Vdc for up to 5 min)

Reverse………………………………………………………………..-56 Vdc continuous

Burden………………………………………………………………..18 W, 1 A max.

VVoollttaaggee

SSeennssiinngg

IInnppuuttss

VVoollttaaggee::

120 Vac Input (L-N) Wye PT Configuration………………..65–150 Vac, terminals 4-5. 7–12. 9 –12. and 11–12

240 Vac Input (L-N) Wye PT Configuration………………..150–300 Vac,  terminals 3-5. 6–12. 8–12. and 10–12

120 Vac Open Delta PT Configuration……………………..65–150 Vac, terminals 3-5. 6–8. 8–10 and 10–6

240 Vac Open Delta PT Configuration……………………..150–300 Vac, terminals 3-5. 6–8. 8–10. and 10–6

Phases ………………………………………………………………..Three phase generator bus, single phase parallel bus

Frequency …………………………………………………………..45–66 Hz

Burden………………………………………………………………..Less than 0.1 VA per phase

Accuracy…………………………………………………………….0.1% of full scale

CCuurrrreenntt

IInnppuuttss

Current………………………………………………………………..0–5 A rms

Frequency …………………………………………………………..45 to 66 Hz

Burden………………………………………………………………..Less than 0.1 VA per phase

Accuracy…………………………………………………………….0.1% of full scale

Phases ………………………………………………………………..Three phase generator bus

Discrete Inputs ……………………………………………………..18–40 Vdc @ 10 mA

Relay Driver Outputs………………………………………………18–40 Vdc @ 200 mA sink

Analog Inputs……………………………………………………….4–20 mA @ 243Wor 1-5 Vdc @ 10kW

Local Operating Network……………………………………….Echelon®LonWorksTMTechnology, Standard Protocol, 1.25 MBPS

Calibration and Diagnostics Port …………………………….RS422

CCOOMMPPLLIIAANNCCEE

UL/cUL………………………………………………………………….Listed

Woodward Digital Synchronizer and Load Control (DSLC) ADJUSTMENTS

ADJUSTMENTS

The Woodward Hand Held Programmer makes all

adjustments quickly and easily, through the control’s ten

convenient “menus”.  The control saves all set points in

permanent memory, which does not require batteries or

other power sources to retain data.  The Hand Held

Programmer prevents tampering with set points, yet allows

entries to be changed at any time.

• Menu 1 – Synchronizer Functions

• Menu 2 – Load Control Functions

• Menu 3 – Process Control Functions

• Menu 4 – VAR/Power Factor Control Functions

• Menu 5 – Configuration

• Menu 6 – Calibration

• Menu 7 – Generator Electric Parameters

• Menu 8 – Control Status Monitor

• Menu 9 – Discrete Inputs/Outputs Monitor

• Menu 0 – Diagnostics

Woodward Digital Synchronizer and Load Control (DSLC) OPERATING MODES

OPERATING MODES

Isolated Bus — The DSLC talks over its LON to share

proportional real and reactive loads.  Real load (kW) is

controlled using percentages of full load for each machine,

and reactive loads (kVAR) are

shared by matching power factors.

The DSLC maintains a specified

bus voltage and frequency while

balancing loads.

Utility Parallel — The DSLC

measures real load (kW) on the

generator and adjusts the speed

control to match a set base load, to

control a process at a user-chosen,

externally adjustable setpoint.  Or it

can set a constant import/export

level using an MSLC ( Master

Synchronizer and Load Control).

The DSLC can also measure and

maintain a set reactive load (kVAR)

or can maintain a user-prescribed

power factor.

Transition Between Modes — The

DSLC will ramp at a user-chosen

rate from one mode to another

until the control is within 5% of its

target. It then shifts into dynamic

control, allowing bumpless

operating mode changes. In

addition, the DSLC automatically

changes its VAR/PF mode when

the real load mode is changed to or

from an isolated bus, load sharing

mode. Manual VAR/PF control

may also be selected.

Woodward Digital Synchronizer and Load Control (DSLC) ADVANTAGES

ADVANTAGES

• Reduces wiring between synchronizer, load

control and automatic loading controls

• Having functions integrated into one box

eliminates the need for redundant sensors

(like PTs, CTs and MOPs) that connect to

individual modules such as the load sensor and synchronizer

• Hand Held Programmer reduces installation

and calibration time by allowing the user to

set up the control prior to starting the system

• Hand Held Programmer lets operator monitor generator

parameters, contact switches, and analog I/O for

installation and troubleshooting

• Reduces the amount of cabinet space needed

• Eliminates the need for additional relay logic or a PLC to

control dead bus closing

• Digital communications across the LAN reduce

susceptibility to noise on the load sharing lines

• Slip frequency paralleling, voltage matching, and speed

bias hand-off between the synchronizer and load control

result in smooth paralleling without the risk of reverse power trips

• Three-phase true rms power sensing makes the DSLC

accurate even with unbalanced phase loading and voltage fluctuations

• Can load share with Woodward analog controls when

used with the Load Sharing Interface Module. Refer to

Woodward Manual # 02031 for details.

Woodward Digital Synchronizer and Load Control (DSLC) APPLICATION

APPLICATION

The Woodward DSLCTM control is a

microprocessor-based synchronizer and load

control designed for use on three-phase AC

generators equipped with Woodward or other

compatible speed controls and compatible

automatic voltage regulators. The DSLC is a

synchronizer, a load sensor, a load control, a

dead bus closing system, and optionally a

VAR/PF and process control, all integrated

into one powerful, yet convenient package.

The DSLC control provides either phase

matching or slip frequency automatic

synchronizing. The DSLC talks over its own

LON (using Echelon®  LonWorks™* network

technology) to enable safe dead bus closing,

and ties into your automatic voltage regulator

to match voltages before paralleling.

The DSLC control senses true rms power and

provides bumpless loading and unloading

functions.  It can either base load or set

import/export/process power levels against the

utility, and through the DSLC’s LON,

accurately share loads on isolated, multi-engine

systems.

The optional VAR/PF control is flexible

enough to allow you either to provide a set

level of VARs to the utility (if this is

economical) or to maintain a constant power

factor for reliable operation.  Through the

LON, the VAR/PF control also shares power

factors in isolated systems, maintaining

proportional reactive loads (kVARs) on all

machines more accurately than droop or cross

current voltage systems.

Woodward will provide update files for legacy DSLC-2 and MSLC-2 devices Schedule

The important control functions run on the same task rates that ensures the same control dynamic.

Most important, it is being designed to be able to run with the legacy DSLC-2/MSLC-2 system.

This becomes more important than ever due to lack of obtainable components that may

force us to make a hard stop to the DSLC-2/MSLC-2 product line later this year.

If some minor rules are observed the DSLC-2XT can be mixed with already existing DSLC-2 / MSLC-2 in an application.

MSLC-2XT (in line with DSLC-2XT) is also in preparation and comes few months after DSLC-2XT.

Others:

The communication 9-pin D-sub connectors are replaced by phoenix plugs with screw terminals

The analog outputs 1 & 2 are supported with two terminals now (the shunt for voltage output is internally populated)

Schedule:

DSLC-2XT: Design release to production scheduled for Sept’22.

Shipment expected Oct’22 however depends on availability of components.

Limited early sample and draft manual available. Please contact your account manager.

MSLC-2XT: Design release to production scheduled for Nov’22.

Shipment expected Dec’22 however depends on availability of components.

Limited early sample and draft manual available. Please contact your account manager.

Part Numbers:

8440-2298: MSLC-2XT

8440-2299: DSLC-2XT

Woodward Communicating with legacy DSLC-2 (and MSLC-2) General

General:

The DSLC-2XT/MSLC-2XT is an upward compatible successor device for the DSLC-2/MSLC-2.

They are based on the easYgen-3400XT-P2 hardware. It is designed to function

as good as the original DSLC2/MSLC-2 (version 1.1511).

The new generation is equipped with a more powerful CPU, memory, and communication.

It is more responsive in HMI and SCADA communications.

The important control functions run on the same task rates that ensures the same control dynamic.

Most important, it is being designed to be able to run with the legacy DSLC-2/MSLC-2 system.

This becomes more important than ever due to lack of obtainable components that may

force us to make a hard stop to the DSLC-2/MSLC-2 product line later this year.

If some minor rules are observed the DSLC-2XT can be mixed with already existing DSLC-2 / MSLC-2 in an application.

MSLC-2XT (in line with DSLC-2XT) is also in preparation and comes few months after DSLC-2XT.

Others:

The communication 9-pin D-sub connectors are replaced by phoenix plugs with screw terminals

The analog outputs 1 & 2 are supported with two terminals now (the shunt for voltage output is internally populated)

Woodward Communicating with legacy DSLC-2 (and MSLC-2)

Important Considerations:

Communicating with legacy DSLC-2 (and MSLC-2)

Woodward will provide update files for legacy DSLC-2 and MSLC-2 devices in the field if

there is to run a mix of both DSLC-2/MSLC-2 generations.

The legacy device will then send their UDP messages in a way that DSLC-2XT/MSLC-2XT can evaluate.

It is mandatory to load this update file into the legacy devices for the system to run smoothly.

2. Using your existing settings file (*. WSET) from legacy DSLC-2 (and MSLC-2)

Woodward will provide a conversion rule for ToolKit to make the configuration transfer as smooth as possible.

Some minor parameters will be shown in a log file, to be evaluated manually.

3. The AC measurement of the DSLC-2XT (and MSLC-2XT)

The measurement hardware and software are different in comparison to the legacy devices.

This is mainly due to higher accuracy, more flexible measurement range and fast response characteristics.

The earthing of the DSLC-2XT/MSLC-2XT devices has become more important due to higher impedance of the measurement circuits.

4.ToolKit

To give you a seamless transition experience, the ToolKit layout (*. WTOOL file) is designed like the original devices.

There are few less parameters due to new AC measurement and communication interfaces.

5.Documentation server

Product literature (manuals, config. files, software etc.) is hosted on a documentation server

that is easily accessible by a QR code printed on the housing.

Two additional QR stickers are delivered with the controllers to help you paste them at a location convenient to you.

Subsequently, product CD is removed from scope of delivery.

What are the differences between DSLC-2 MSLC-2 and DSLC-2XT MSLC-2XT ?

Woodward understands the time-intensive nature of Power Generation projects.

Ensuring the longevity of our products is one way we make our customers successful.

Woodward has supplied and supported the field proven MSLC-2/DSLC-2 line of

synchronizers and load controllers for over a decade.

An upcoming state of the art Drop-In replacement successor extends the life cycle of this product line for another decade and

possibly beyond. This document provides an overview of what to expect from the successor products,

namely MSLC-2XT/DSLC-2XT respectively.

Important Features:

→  Drop-In Replacement (Mounting dimensions and overall dimensions are same)

→  Similar Look and Feel as MSLC-2/DSLC-2 (available in back panel mounting style)

→  USB Connectivity to PC (RS-232 port is removed; new: USB Type B)

→  Direct connect up to 690VAC (increased range handled by device configuration)

→  Software selectable 1A/5A CT input (supported by one P/N)

NE810 ABB Ability™ System 800xA® hardware selector

NE810 is an Industrial switch made for harsh environments. Due to

our multi-rate SFP solution, the switch can be used in either 100

Mbit or Gigabit networks. Our unique FRNT (Fast Recovery of

Network Topology) technology is the fastest protocol on the

market to re-configure a network in case of any link or hardware

failure. That is why NE810 is also used in safety-critical applications

such as tunnels, traffic signal control, and railway systems.

Installations in harsh environments and places with heavy electrical

interference require the use of reliable media. NE810 provides a

number of solutions using fiber optic transceivers. Multi- or singlemode

transceivers can be used to build point-to-point or

redundant ring networks with ranges up to 120 km between each

switch. Our BIDI transceiver, which transmits and receives data on

a single fiber can be used in applications where the number of fiber

cores is limited.

Real-time properties are implemented in the switch in order to

achieve determinism for real-time critical applications. NE810

supports QoS (Quality of Service) with four priority queues and

strict priority scheduling as well as HoL (Head of Line Blocking

Prevention). All to assure that the data network is deterministic.

Search for products