Features
• Main board of AutroSafe ready for subrack mounting
• Designed to meet the requirements of: – EN54-2 – IACS UR E10
– IMO/SOLAS – FM /NFPA72 – IEC61508 SIL2 (116-BC-440G2 only)
• Subrack 3Ux12HP, 200mm deep
• Fault Output Relay
• Redundant Power Input, monitored
• Serial port RS232/RS422/RS485
• AutroFieldBus
• Redundant Ethernet
Capacity
• 31 BC-440 per system
• 15000 loop units per system
• 30 I/O modules can be connected to one I/O stack if BSL
310A is used (12 I/O modules if BSL-310 is used)
• 12 loop driver modules can be connected to one panel
• 512 loop units can be connected to one I/O-stack
• 1024 loop units can be connected to one panel (a total of
512 detectors and/or manual call points if EN 54 approval is
required)
• 31 AutroFieldBus units can be connected to AutroFieldBus
• 127 loop units can be connected to one detection loop
• 15 loop units can be connected to one Powerloop