Features

 1 Mimic Driver is capable of driving 32 current

limited LEDs

 1 Mimic Driver is provided with 8 standard

monitored inputs

 A maximum of 8 Mimic Drivers can be connected

to the RS-485 Panel Bus, providing a total of 256

outputs and 64 monitored inputs

 Powered by 24 VDC, redundant, monitored

 Lamp test

 LED intensity control

 Snap-on to DIN rail (TS-35)

 Designed to meet EN 54 and SOLAS

requirements, and conforms to CE standards

Switch Settings Failsafe and line Termination

Master and the last* Slave: The switches S2.1. S2.2

and S2.3 are to be set to ON.

Other Slaves: The switches S2.1. S2.2 and S2.3 are

to be set to OFF.

*Refer to connection Overview – Master/Slave

Drivers.

X2 Panel Bus Address Switch

If S2.7 is set to Master, X2 sets the panel bus

address. If S2.7 is set as a slave, X2 sets the RS

485 daisy-chain slave address. The range for the

switch is 1-9.