LED Indicators
These LEDs are lit when conditions are met to close the breaker:
• Bus Upper Voltage Limit OK
• Gen/Line Upper Voltage
Limit OK
Breaker Close Relays
• Bus Lower Voltage Limit OK
• Gen/Line Lower voltage
Limit OK
• ∆V Limit OK
• ∆F Limit OK
• M-0193B Ready
Dry output contacts rated to make and carry 20 A up to 250 V dc, interrupt 0.9 A, 120 V dc inductive load;
0.4 A, 250 V dc inductive load. Open contacts or contacts to ground will withstand 1500 V ac for one minute.
Status Contacts
Relay contacts; closed indicates ∆F conditions OK
Relay contacts; closed indicates ∆V conditions OK
These are light duty contacts intended primarily for status interrogation by supervisory control They can be
used to light local lights with the following maximum restrictions: 1/2 A at 125 V dc resistive, 1 A 120 V ac,
250 V dc across open contacts
Minimum Frequency Difference
The guaranteed minimum frequency difference for operation is 0.0005 Hz; however, typical units consistently
operate with frequency differences of 0.0001 Hz.