• Accurate, independent controls require
no additional instrumentation for field setting
• Various ∆V and ∆F limits available
• Breaker closing times are field programmable
• 50 Hz operation available
Inputs
Gen/Line Voltage, nominal 120 V ac, 145 V ac maximum continuous. Will withstand 200 V ac for 1 sec.
Bus Voltage, nominal 120 V ac, 145 V ac maximum continuous. Will withstand 200 V ac for 1 sec.
Supply Voltage, minimum 100 V ac, maximum 140 V ac.
Enable Auto-Sync close.
Breaker Closing Time; field programmable from 20 to 800 ms.
NOTE: Gen/Line, Bus and Supply voltages are transformer-isolated to allow complete freedom in
applications.
Burden
Gen/Line or Bus: 0.5 VA maximum at 120 V ac
Supply: 7 VA maximum at 120 V ac
Controls
UPPER VOLTAGE LIMIT (either input): 110 to 140 V ac, accuracy 1–1/2% of full scale
LOWER VOLTAGE LIMIT (either input): 90 to 120 V ac, accuracy 1–1/2% of full scale
∆V LIMIT (MAXIMUM VOLTAGE DIFFERENCE LIMIT): 1 to 5 V ac, accuracy 5% of full scale. Multiples of
this range are available. A ∆V LIMIT of 4 to 20 V ac or lower must be specified if the M-0193B is to be used
in conjunction with the M-0194 Generator Control Unit.
∆F LIMIT (Maximum Frequency Difference Limit): 0.05 to 0.5 Hz, accuracy 3% of full scale. An additional
range of 0.005 to 0.05 Hz is available.