Configurable DC Power Monitoring

Four analog inputs allow the user to remotely monitor DC voltages from 0 to

30 Vdc. Each input can be configured with two setpoints to report when voltage

drops below the specified levels. The analog to digital converter is 12 bit and

averaging is done over 128 samples to increase resolution to 16 bits.

Analog metering data is updated every 64 ms.

Turn-on/off Battery Load Test Command

Test frequency is user defined in the Battery Charger common setpoints in

IPScom communication software.

The M-7679 R-PAC issues the “Turn-on/off Battery Load Test” command to the

M-2035 to test the battery capacity only when the charger is operating from

the main power supply.