Configurable DC Power Monitoring
Four analog inputs allow the user to remotely monitor DC voltages from 0 to
30 Vdc. Each input can be configured with two setpoints to report when voltage
drops below the specified levels. The analog to digital converter is 12 bit and
averaging is done over 128 samples to increase resolution to 16 bits.
Analog metering data is updated every 64 ms.
Turn-on/off Battery Load Test Command
Test frequency is user defined in the Battery Charger common setpoints in
IPScom communication software.
The M-7679 R-PAC issues the “Turn-on/off Battery Load Test” command to the
M-2035 to test the battery capacity only when the charger is operating from
the main power supply.