Options
SCADA CUTOUT switch allows Local blocking of SCADA commands (for use with SCADA enabled M‑2001
controls). Use of the SCADA Cutout switch with the M-2001C, requires a M-2001C Control with firmware
version D‑0146V08.01.22 or later installed.
SCAMPTM (SCADA Controllable Auto/Manual Pushbutton) switch allows the Auto/Manual state on the adapter
panel to be changed by a SCADA command. Use of the SCAMP pushbutton switch with the M‑2001C,
requires a M-2001C Control with firmware version D-0146V08.05.XX or later installed.
Voltage Reduction switch allows 2 levels of Voltage Reduction to be selected.
Testing Specifications
High Voltage: All input and output terminals will withstand 1500 Vac rms to chassis or instrument ground for
one minute with a leakage current not to exceed 25 mA, for all terminals to ground. Input and output circuits
are electrically isolated from each other, from other circuits and from ground.
Surge Withstand Capability: All input and output circuits are protected against system transients. Units
pass all requirements of ANSI/IEEE C.37.90.1-1989 defining surge withstand capability.
Radiated Electromagnetic Withstand Capability: All units are protected against electromagnetic radiated
interference from portable communications transceivers.