Testing Specifications
High Voltage: All input and output terminals will withstand 1500 Vac rms to
chassis or instrument ground for one minute with a leakage current not to
exceed 25 mA, for all terminals to ground. Input and output circuits are
electrically isolated from each other, from other circuits and from ground.
Surge Withstand Capability: All input and output circuits are protected against
system transients. Units pass all requirements of ANSI/IEEE C.37.90.1-1989
defining surge withstand capability.
Radiated Electromagnetic Withstand Capability: All units are protected against
electromagnetic radiated interference from portable communications transceivers.
Environmental
Temperature Range: Functionality is maintained from -40° to +85° C.
Humidity: Functionality is maintained under 95% relative humidity (non-condensing).
Fungus Resistance: A conformal printed circuit board coating inhibits fungal growth.
Physical
M‑2302 Adapter Panel – Specification
Size with M‑2001 Series Digital Tapchanger Control: 16.00″ high x 9.50″
wide x 4.185″ deep (40.6 cm x 24.13 cm x 10.5 cm)
Approximate Weight: 2 lbs, 7 oz (1.11 kg)
Approximate Shipping Weight: 5 lbs, 7 oz (2.47 kg)
Approximate Weight with M‑2001 Series Digital Tapchanger Control: 6 lbs, 2 oz (2.78 kg)
Approximate Shipping Weight with M‑2001 Series Digital Tapchanger Control: 11 lbs, 2 oz (5.05 kg)
Leave a comment