Description

The Rack Interface Module (RIM) is the primary interface to the 3500 rack. It

supports a proprietary protocol used to configure the rack and retrieve

machinery information. The RIM must be located in slot 1 of the rack (next to the

power supplies).

The RIM supports compatible Bently Nevada external communications

processors such as TDXnet, TDIX, and DDIX. While the RIM provides certain

functions common to the entire rack, the RIM is not part of the critical monitoring

path and has no effect on the proper, normal operation of the overall monitoring

system. One RIM is required per rack.

For Triple Modular Redundant (TMR) applications, the 3500 System requires a

TMR version of the RIM. In addition to all the standard RIM functions, the TMR RIM

also performs “monitor channel comparison.” The 3500 TMR configuration

implements monitor voting using the setup specified in the monitor options.

Using this method, the TMR RIM continually compares the outputs from three (3)

redundant monitors. If the TMR RIM detects that the information from one of

those monitors is no longer within a configured percentof the information of the

other two monitors, it will flag that the monitor is in error and place an event in

the System Event List.