Welcome to the official website of CNIACS Automation Technology Co., Ltd!

Emerson M-series Virtual I/O Module PROFINET

PROFINET

The VIM2 with the PROFINET Driver acts as an I/O

Controller in a PROFINET network, exchanging data with

I/O Devices using Real-Time (RT) messaging. Isochronous

real-time (IRT) communication is not supported. The driver

supports the PROFINET v2.2 specification and emulates

Profibus DP cards on the DeltaV I/O bus.

Field device communications comprise I/O data, alarms,

and diagnostics. Other aspects of field data, e.g., data

records and logbook information, are not supported.

Alarm and diagnostic data are reported to PC-based

VIMNet Explorer tools. Only I/O data and corresponding

status are reported to the DeltaV controller.

The VIM2 with the EtherNet/IP Driver provides the following

compatible functions using the Common Industrial Protocol

(CIP) as defined in the EtherNet/IP Specification from

Open DeviceNet Vendor Association (ODVA) and ControlNet

International. The driver emulates either Programmable

Serial cards or DeviceNet cards on the DeltaV I/O bus.

Emerson M-series Virtual I/O Module 2 EtherNet/IP

EtherNet/IP

The VIM2 with the EtherNet/IP Driver provides the following

compatible functions using the Common Industrial Protocol

(CIP) as defined in the EtherNet/IP Specification from

Open DeviceNet Vendor Association (ODVA) and ControlNet

International. The driver emulates either Programmable

Serial cards or DeviceNet cards on the DeltaV I/O bus.

The VIM2 EtherNet/IP Scanner Driver provides:

I/O Scanner (Transport Class 1 originator,

using connected implicit messaging).

I/O Adapter (Transport Class 1 target, using connected

implicit messaging).

Unconnected explicit (UCMM) messaging client.

Connected explicit (Transport Class 3 originator) messaging client.

Emerson M-series Virtual I/O Module Rockwell PLC Scanner

FMC722 Subsea

The VIM2 with the FMC722 Driver supports

communications with FMC Technologies Topside Processing

Unit (TPU) using the FMC722 (TPC) protocol.

Code 1 – Read Coil Status

Code 2 – Read Input Status

Code 3 – Read Holding Registers

Code 4 – Read Input Registers

Code 5 – Force Single Coil

Code 6 – Preset Single Register

Rockwell PLC Scanner

The VIM2 with the Rockwell PLC Scanner Driver provides

the following compatible functions using the Common

Industrial Protocol (CIP) as defined in the EtherNet/IP

Specification from Open DeviceNet Vendor Association

and ControlNet International. This driver emulates

Programmable Serial cards on the DeltaV I/O bus.

The VIM2 EtherNet/IP Scanner Driver provides:

IO Adapter (Transport Class 1 target, using connected

implicit messaging). Supported in simplex or

dual simplex configurations.

Unconnected explicit (UCMM) messaging client

Embedded DF1 (PCCC). Supported in simplex,

dual simplex, and redundant configurations.

Emerson M-series Virtual I/O Module 2 Modbus TCP

Supported Industrial Ethernet Protocols

Modbus TCP

The VIM2 with the Modbus TCP Driver supports the

following Modbus communications protocol function codes

to read and write values to and from Modbus devices,

as specified by the Modbus Application Protocol

Specification from Modbus-IDA.org. This driver emulates

Programmable Serial cards on the DeltaV I/O Bus.

The VIM2 Modbus TCP/IP Driver supports the following

Modbus function codes:

Code 8 – Diagnostic Loop Back Test

Code 15 – Force Multiple Coils

Code 16 – Preset Multiple Registers

The VIM2 can function as both a Modbus TCP master

and slave simultaneously. Master or slave mode is set

at the virtual port level. The master and slave capability

are available in simplex implementations; in redundant

applications, only master mode is supported.

Emerson M-series Virtual I/O Module VIM2 Dual Simplex or Redundant Setups

VIM2 Dual Simplex or Redundant Setups

Two VIM2s can either be setup as a dual simplex or

redundant pair for installations that either consists of

many field devices or require additional communication

resiliency, respectively.

If two VIMs are configured for dual simplex operation, both

VIM2s will work as Standalone units and no redundancy link

cable is installed.

If two VIMs are configured for redundant operation, the

active and standby VIM2s monitor each other with a

continuous status command using the redundancy link

cable supplied with each redundant pair. The active VIM2

communicates over the network to the Industrial Ethernet

device and the standby sends an intermittent signal to the

device to maintain communication integrity.

The Ethernet I/O drivers are available separately from the

VIM2 hardware. Each operating VIM requires one license

for the running protocol. For example, a redundant pair of

VIMs requires two copies of the driver running on that pair,

but an offline spare does not require licensing.

Emerson M-series Virtual I/O Module 2 VIMNet Explorer

VIMNet Explorer

VIMNet Explorer allows the user to commission the VIM2;

setup primary, secondary, and/or redundant VIM2s; define

the Ethernet I/O network; and view advanced diagnostics

information. The user can specify the IP address, Subnet

Mask, and Gateway of each VIM2 and set the node address

and names of each Ethernet I/O device integrated with

the VIM2. VIMNet Explorer is also used to flash upgrade a

VIM from one version of a driver to another or to replace

an existing driver type with another. Only one Ethernet I/O

driver may be loaded in the VIM2 at one time.

VIMNet Explorer application must run on a workstation

that has network connectivity to the Ethernet I/O network.

This may be a DeltaV workstation with the third network

interface card (NIC) connected to the Ethernet I/O network

or may be a non-DeltaV workstation. Connection to the

VIM2 is done through the RJ-45 Network Connection on the

bottom of the VIM2.

VIMNet Explorer installation media is downloadable from Guardian.

Emerson M-series Virtual I/O Module Ethernet I/O Integration

Ethernet I/O Integration

When used with the Ethernet I/O drivers, the VIM2

can communicate with high-speed Ethernet networks

over Modbus TCP, EtherNet/IP, FMC722. or PROFINET.

Depending on redundancy configuration of the VIM2. the

DeltaV controller auto-senses a commissioned VIM2 as four

or eight DeltaV I/O Cards.

• In simplex installations these cards will be sensed in slots 57-60 or 61-64.

• In dual simplex installations these cards will be sensed in slots 57 to 64.

• In redundant installations the redundant pairs will be sensed in slots 57 to 64.

Users configure the I/O signals for commissioned VIM2s

in DeltaV Explorer in the same manner as a DeltaV Serial, DeviceNet, or Profibus Card.

Emerson M-series Virtual I/O Module 2 Product Description

Product Description

The VIM2 may be used for either DeltaV I/O simulation or

Ethernet I/O device integration. The VIM2 mounts on a

2-wide horizontal or 4-wide vertical carrier on either side

of the DeltaV controller. A dedicated DeltaV system power

supply is required.

IO Simulation

When used with DeltaV Mimic software, the VIM2

supports I/O simulation all DeltaV M-series I/O cards

including classic IO, FOUNDATION Fieldbus, Profibus DP,

DeviceNet, ASi-bus and Serial.

Mimic provides dynamic simulation for DeltaV system

software acceptance testing and operator training. Mimic

works by simulating the DeltaV I/O. It also simulates field

devices using Foundation Fieldbus, Profibus DP, DeviceNet,

and AS-i buses. For Mimic to do this, the physical I/O cards

are disconnected from the control system. The Mimic driver

writes to the I/O subsystem of the DeltaV controller. Process

models in Mimic simulate realistic process reactions to

control system output signals.

Each offline process controller uses one Mimic simulation

node and VIM. The I/O simulation driver is available with Mimic.

Emerson M-series Virtual I/O Module 2 Benefits


Specific ease of use features include:

 Automatic updates. Simulation I/O driver updates for the VIM2 are included with the MiMiC software

releases.

Updates are quick and easy over the simulation network.

 Seamless Ethernet I/O integration. When used with the MYNAH Ethernet I/O drivers,

the VIM2 is seen by the DeltaV M-series controller as four DeltaV Serial Cards.

Commissioned VIM2s are auto-sensed by the DeltaV controller as DeltaV Serial Cards.

 Configured in DeltaV Explorer. Serial dataset configuration used for Ethernet I/O integration

is done in the DeltaV Explorer in the same manner as a DeltaV Serial Card.

Ethernet I/O signals can be used in DeltaV Control Modules, displayed on 

DeltaV Operate graphics and stored in the DeltaV Continuous Historian.

 Intuitive setup. The VIMNet Explorer application provides plug-n-play capability making setup of the VIM2 easy and intuitive. 

Graphical, drag-n-drop, functionality makes setting up multiple VIM2s almost effortless. 

VIMNet Explorer is integrated with DeltaV Explorer to make setup of the VIM2 easy and intuitive.

Modular, flexible packaging. The VIM2 mounts in the same manner as the DeltaV controller.

It mounts in the controller slot of a DeltaV 2-wide horizontal or 4-wide vertical carrier and uses a standard DeltaV Power Supply.

The advanced design of the VIM2 will provide years of uninterrupted use.

Emerson M-series Virtual I/O Module Easy to use

The VIM2 and the Ethernet I/O devices must be on the same IP subnet to communicate.

 1:1 Redundancy. Redundancy can be added to any Ethernet I/O system by adding a second

VIM2 and configuring the two cards as a redundant pair.

The VIM2 appears as four redundant DeltaV Serial Card pairs.

Automatic switchover of primary to standby cards is handled like the DeltaV Serial Card.

The operator is given clear notification of a switchover at the operator display.

Manual switchover can be controlled in DeltaV Diagnostics.

Easy to use. The VIM2 is easy to use and well integrated into the DeltaV system.

VIMNet Explorer is integrated with DeltaV Explorer to make setup of the VIM2 easy and intuitive.

Modular, flexible packaging. The VIM2 mounts in the same manner as the DeltaV controller.

It mounts in the controller slot of a DeltaV 2-wide horizontal or 4-wide vertical carrier and uses a standard DeltaV Power Supply.

The advanced design of the VIM2 will provide years of uninterrupted use.

Search for products

Back to Top
Product has been added to your cart