Welcome to the official website of CNIACS Automation Technology Co., Ltd!

GE MVAJ 31 Tripping and Control Relays

Operation

When the relay is switched  the high speed unit will operate inside 4 milliseconds followed

shortly after by the MVAA. The outgoing contacts of the two units are in parallel so to give

high speed and the breaking capacity. By using a low value resistor in parallel the 10 uF

capacitor discharge is overcome. As the MVAA 11 operates it switches out the MVAA16

and parallel resistor to lower the burden to an acceptable level.

Results

Pick up range: 87.5-  137.5V

Pick up time: 4 milliseconds  over voltage range

Drop off time: 15 milliseconds

Initial Burden  180 watts at 137.5 volts for 4 milliseconds  reducing  to 65 watts and finally

6.8 watts after 15 milliseconds.

GE MVAJ 31 Key Benefits

The MVAJ31 is built on similar lines to the MVAA 16 and followed by an MVAA11 using a

mixture of standard  and heavy duty contacts. In order to meet the capacitor discharge

test some resistors and internally  wired contacts  have been added.

Case Size

The relay may be housed in either  MIDOS  size 3 or size 4 cases. The heavy duty contacts

are as for the MYAA II  so the same contact duties can be claimed.  All other outgoing

contacts  are as standard  MVAAs.

Key Benefits

• High speed operation

• High and low burden alternatives

• Models surge proof against high capacitance discharge currents in the dc supply system,

are available

• Control relays immune to AC can be supplied

GE MVAJ 11 to 34 Tripping and Control Relays

Description

Low Burden Tripping Relay Types MVAJ 11. 13. 14

These relays are suitable for applications where immunity to

capacitance discharge and high minimum operation currents are

not required.

Control Relay Type MVAJ 34

This is a dual-rated electrical-reset relay, the main function of

which is to switch protection and autoreclosing equipment in and

out of service from a remote point via pilot wires. It complies with

NGC SPEC. NGTS2.19:1996.

High Burden Tripping Relay Types MVAJ 21. 23. 25. 26. 27

Versions have one or two contact stacks depending on the number

of output contacts required.

Type MVAJ 21 High Burden Self-resetting Relay

This uses a contact on the main contact stack to energize a

separate, rear-mounted economizing element. After operation,

this reduces the burden by switching in resistance in series with

the main element and switching out shunt resistance.

Figure 2 shows a typical circuit diagram for self-resetting relays of

this type with high speed economy. When the main attracted

armature unit RL1 is energized by the protection contact PR, a

contact RL1-a energizes auxiliary element RL2. When contacts

RL2-a and RL2-b open, resistor R4 is put in series with RL1 while

the circuit to resistor R2 is broken.

GE High Burden Tripping Types MVAJ 21. 23. 25. 26. and 29

High Burden Tripping Types MVAJ 21. 23. 25. 26. and 29

These relays are suitable for use in high security circuit breaker tripping circuits.

particular they can be used in distributed tripping or control relay contact logic

where the initiating contact may be remote from the relay. The relays have a high

which is either cut-off at operation or economized to a low figure, either

or after a time delay.

The high burden provides immunity to capacitance discharge currents, which can result

the inception of an earth fault on battery wiring and immunity to the subsequent

current.

The high burden also permits the use of supervision relays such as type MVAX where

wiring is at risk and provides reliable operation of series elements such as repeat

type MCAA. For the latter purpose, type MVAJ relays can be provided with a time

economizing feature.

Control Relay Type MVAJ 34

This is a dual-rated electrical-reset relay, the main function of

which is to switch protection and autoreclosing equipment in and

out of service from a remote point via pilot wires. It complies with

NGC SPEC. NGTS2.19:1996.

GE MVAJ 11 to 34 Tripping and Control Relays

The MVAJ 11 to 34 range complements the more cost-effective range of MVAJ 051 to

MVAJ 205 tripping relays catering for the preferences of historical users.

MVAJ general characteristics can be found in table 1 that includes information on how

relay burden is modified at, or just after operation. ‘Economy’ indicates that the burden

reduced to a low value.

Instantaneous cut-off is a feature of some hand and electrical-reset elements and

the burden to zero, whilst others incorporate a time delay to enable series elements

operate. This time delay is 40 ms to 60 ms in all cases, except that of  type MVAJ 26

the delay is 2 s. All low burden relays are suitable for AC or DC operation. All high

relays are for DC operation only.

Types MVAJ 23. 25 High Burden Tripping Relays

with Instantaneous Cut-off

These relays incorporate a break contact in series with the

operate coil. Located on the main contact stack, it is arranged to

break the coil circuit once the relay mechanism has completely

operated. This reduces the relay burden to zero as soon as

mechanical latching of the contacts has occurred.

GE MVAJ 05/10/20 Tripping and Control Relays

MVAJ 10. MVAJ 20

When configured for high burden applications, the burden is

either cut off or is economised to a low figure after a 40-60 ms

time delay. Due to the greater minimum operating current, the

high burden application also permits the use of supervision relays

such as type MVAX 11. where the wiring is at risk. The 40- 60 ms

time delay ensures reliable operation of series elements such as

type MCAA repeat relays.

Type MVAJ 102 relay is specifically designed for applications

requiring a tripping relay which is self-resetting after a nominal

delay of 2.5 seconds. This relay may be used, for example, for

inter-tripping between higher voltage and low voltage circuit

breakers of a large 3-phase power transformer.

This may become necessary when the high voltage circuit

breaker is tripped after a heavy internal fault by protection

which cannot conveniently provide an auxiliary contact with a

dwell time long enough to ensure correct tripping of the low

voltage circuit-breaker.

Typically, the relay is initiated by transformer protection, such as

overall protection, restricted earth fault and Bucholz relays, in

arrangements where both the HV and LV circuit-breakers are to

be tripped simultaneously.

The HV breaker may be expected to trip more quickly than the LV

breaker so the tripping signal is maintained by the delayed reset.

This ensures complete clearance by the LV circuit-breaker, even

though the fault may have been cleared largely by the HV breaker

and the protection has started to reset.

GE MVAJ 05/10/20 High Burden Application

High Burden Application

These relays, supplied as high burden, are suitable for use in high

security circuit-breaker tripping circuits. The high burden provides

greater immunity to capacitance discharge currents, which can

result at the inception of an earth fault on battery wiring. This

makes the relays particularly suitable for use in distributed

tripping or control relay contact logic schemes, where the

initiating contact may be remote from the relay.

MVAJ 05

When configured for high burden applications, the burden is

either cut off at operation or is economised to a low figure

instantaneously.

Low Burden Application

These relays are suitable for general applications where the

initiating contact is located close to the relay. When configured

for low burden applications, by removing the external link from

terminals 22 and 24. the burden is either cut off during operation

or is economised to a low figure instantaneously.

GE MVAJ 05/10/20 Models Available

Models Available

• Trip relays

Trip relays possess a standard hand-reset flag and operate within 10 ms.

Table 1 shows  the trip relay versions available

• Control relays

Control relay variants of each trip relay are available. These relays operate within

approximately 15 ms

All relays configured for high burden applications are suitable for DC operation only

Applications

Self-reset relays reset when the initiating signal is removed,

making them suitable for use as trip relays in auto-reclose

schemes and also for general flagging purposes. Hand-reset relays

require manual resetting, making them effective lockout relays

which are commonly used to trip circuit-breakers associated with

transformers. Electrical-reset relays require a voltage to be

applied to the unit to reset the contacts. These relays may be

used in auto-reclose schemes, or where remote resetting of the

relay is required.

Trip Relay

With the exception of the MVAJ 102 time delayed self-reset

relays, all trip relays are suitable for either low burden or high

burden applications.

GE MVAJ 05/10/20 Low Burden Application

Protective relays are precise measuring devices, the contacts of which

should not be expected to switch large electrical loads.

In some cases, the protective relay can trip a circuit- breaker directly,

or according to coil rating and the number of circuits to be energised.

The MVAJ relay interfaces with the protection to provide: higher contact

additional contacts for tripping multiple circuit-breakers, control functions,

signalling interlocking.

The MVAJ range comprises very reliable hinged armature relays designed

to operate circuit-breaker trip coils. Built to very high specifications, the

MVAJ range a highly flexible and reliable link between the protective relays

and the circuit-breakers.

Low Burden Application

These relays are suitable for general applications where the

initiating contact is located close to the relay. When configured

for low burden applications, by removing the external link from

terminals 22 and 24. the burden is either cut off during operation

or is economised to a low figure instantaneously.

GE AT868-2-1-1 Panametrics Ultrasonic Liquid Flow Transmitter

Applications

Le transmetteur de débit pour liquide AquaTrans

AT868 est un système de mesure de débit à

ultrasons complet des liquides suivants:

• Eau potable

• Eaux usées

• Eaux d‘égout

• Eaux de rejet

• Eau traitée

• Eau de refroidissement et de chauffage

• Autres liquides

Caractéristiques

• Mesure du débit non intrusive et économique

• Installation et configuration simples

• Adapté à un large éventail de tailles de conduites

et de matériaux

• Adapté aux conduites à revêtement interne

• Version deux canaux/deux cordes disponibles

• Vitesse d‘écoulement , débit volumétrique et

débit totalisé

• Clavier interne pour la programmation sur site

AT868 Caractéristiques techniques

Performance

Types de fluides

Fluides acoustiquement conducteurs, y compris la plupart

des liquides propres et de nombreux liquides chargés ou

contenant des bulles de gaz. La fraction de vide maximum

dépend du transducteur, de sa fréquence, de la longueur de

la trajectoire et du trajet acoustique des conduites.

Tailles de conduite

• Transducteurs « clamp-on » : 12.7 mm à 7.6 m et plus

• Transducteurs mouillés : 25.4 mm à 5 m et plus

Épaisseur de paroi de conduite

Jusqu‘à 76.2 mm

Search for products

Back to Top
Product has been added to your cart