Sensitive Directional Power
The 889 provides low forward power and reverse power elements
to prevent generator motoring that can cause damage the
prime mover. Independent settings for power pickup levels and
operational delays are available for both alarming and tripping of
each element.
The 889 directional power element responds to three-phase
directional power and is designed for reverse power (32REV) and
low forward power (32FWD) applications for interconnections
involving co-generation.
Loss of Excitation
Supporting application flexibility, the 889 offers two methodologies
to support loss of excitation detection. This can be done through
an impedance-based approach or a Reactive Power approach.
Unlike the Impedance based function, the Reactive Power Function
settings do not need machine parameters for setting and can be
used in cases where machine parameters are not available.