HIMA H6200A DIN rail Safety Analog Isolation Module Transmitter Circuit

HIMA H6200A is a DIN-rail mounted SIL3 certified analog isolating amplifier

with HART transparency, manufactured by HIMA Paul Hildebrandt GmbH.

It provides galvanically isolated power supply for 2-wire field transmitters

and isolates 4–20 mA analog signals to eliminate ground loop interference.

The module supports transparent HART communication for remote

configuration and diagnostics of field instruments. Built-in circuit diagnostics

detect wire break and short-circuit faults. Certified to IEC 61508 SIL3 and

ATEX/IECEx Ex ia, it can be integrated with HIMax and HIMatrix safety

systems for SIS applications including ESD and F&G systems in oil & gas,

petrochemical and power industries.

The combination of the reliable HIQuad I/O modules and the new central

module has been named HIQuad X.

This guarantees maximum compatibility for field installation.

This guarantees maximum compatibility and minimum modernisation effort

in field installations. As HIQuad X is now available, the H41q/H51q central

modules have entered the replacement phase of the HIMA product life cycle.

HIMA DI 24 01 Mounting and Removing the Modules

Mounting and Removing the Modules

To mount and remove the modules, the connection cable clamp terminals must be

unplugged.

Additionally, personnel must be protected from electrostatic discharge. For details, refer to

Chapter 2.1.2.

Mounting the Modules

To mount a module into the rack

1. Insert the module as far as it can go – without jamming it – into the two guiding rails

which are located on the upper and lower part of the enclosure.

2. Apply pressure to the upper and lower extremity of the front plate until the module plugs

snap into the backplane socket.

3. Secure the module with the screws located on upper and lower extremity of the front

plate.

The module is mounted.

Removing the Modules

To remove a module from the rack

1. Remove the plugs from the module front plate.

2. Release the locking screws located on the upper and lower extremity of the front plate.

3 Loosen the module using the handle located on the lower part of the front plate and

remove it from the guiding rails.

The module is removed.

HIMA DI 24 01 HIMatrix Safety-Related Controller

Safety Function

The module is equipped with safety-related analog inputs.

Safety-Related Analog Inputs

The module DI 24 01 has 24 digital input channels for 110 VDC or 127 VAC.

Reaction in the Event of a Fault

If the module detects a fault on a digital input, the user program processes a low level in

accordance with the de-energized to trip principle.

The module activates the FAULT LED.

In addition to the channel signal value, the user program must also consider the

corresponding error code.

The error code allows the user to configure additional fault reactions in the user program.

Start-Up

To start up the controller, it must be mounted, connected and configured in the

programming tool.

HIMA DI 24 01 is a plug-in module for the modular F60 HIMatrix system

Product Description

DI 24 01 is a plug-in module for the modular F60 HIMatrix system.

The module can be inserted in the F60 subrack’s slot 3…8 as many times as required.

Slots 1 and 2 are reserved for the power supply module and CPU module, respectively.

The DI 24 01 module has 24 digital input channels for 110 VDC or 127 VAC that are

galvanically isolated from the I/O bus. The status of the signal inputs is displayed by LEDs

located on the front plate next to the terminal plugs.

The module has been certified by the TÜV for safety-related applications up to SIL 3 (IEC

61508. IEC 61511 and IEC 62061), Cat. 4 (EN 954-1) and PL e (EN ISO 13849-1). Further

safety standards, application standards and test standards are specified in the certificate

available on the HIMA website.

HIMA DIO 24/16 01 Reaction in the Event of a Fault

Reaction in the Event of a Fault

If the module detects a fault on a digital input, the user program processes a low level in

accordance with the de-energized to trip principle.

The module activates the FAULT LED.

In addition to the channel signal value, the user program must also consider the

corresponding error code.

The error code allows the user to configure additional fault reactions in the user program.

Safety-Related Outputs

Each group of 8 outputs is provided with a connector on the clamps for the common

ground.

If an output channel is overloaded, it is switched off for ten seconds until the overload is no

longer present. If the module output range has a total load of more than 8 A, the outputs

are all switched off for 10 seconds and a new test is performed.

Line Control

The digital outputs DO 1 through DO 8 of the DIO 24/16 01 module can be used to monitor

the own digital inputs or the digital inputs of other modules (e.g., DI 32 01) for short-circuits

and open-circuits, e.g., for an EMERGENCY STOP button complying with Cat. 4 in

accordance with EN 954-1. To this end, the outputs are pulsed and connected to the

safety-related digital inputs. In this case, the outputs assume the function of pulsed outputs.

HIMA DIO 24/16 01 Safety-Related Analog Inputs

Safety Function

The module is equipped with safety-related inputs and outputs.

Safety-Related Analog Inputs

Each group of 8 inputs is provided with a common, short-circuit-proof supply LS+ on the

clamps.

The safety-related application (SIL 3 in accordance with IEC 61508) of the inputs and the

sensors connected must comply with the safety requirements. For more information, refer

to the HIMatrix Safety Manual.

Reaction in the Event of a Fault

If the module detects a faulty signal on a digital output, the affected module output is set to

the safe (de-energized) state using the safety switches.

If a fault in the module occurs, all digital outputs are switched off.

In both cases, the module activates the FAULT LED.

The error code allows the user to configure additional fault reactions in the user program.

HIMA DIO 24/16 01 is a plug-in module for the modular F60 HIMatrix system

Product Description

DIO 24/16 01 is a plug-in module for the modular F60 HIMatrix system.

The DIO 24/16 01 module has 24 digital input channels and 16 digital output channels that

are galvanically isolated from the I/O bus. The status of the input and output signals is

displayed by LEDs located on the front plate next to the terminal plugs.

The module can be inserted in the F60 subrack’s slot 3…8 as many times as required. Slots

1 and 2 are reserved for the power supply module and CPU module, respectively.

However, the load on the outputs must not exceed the total current input of the power

supply module.

The module has been certified by the TÜV for safety-related applications up to SIL 3 (IEC

61508. IEC 61511 and IEC 62061), Cat. 4 (EN 954-1) and PL e (EN ISO 13849-1). Further

safety standards, application standards and test standards are specified in the certificate

available on the HIMA website.

HIMA DIO 24/16 01 Reaction in the Event of a Fault

Reaction in the Event of a Fault

If the module detects a fault on a digital input, the user program processes a low level in

accordance with the de-energized to trip principle.

The module activates the FAULT LED.

In addition to the channel signal value, the user program must also consider the

corresponding error code.

The error code allows the user to configure additional fault reactions in the user program.

Safety-Related Outputs

Each group of 8 outputs is provided with a connector on the clamps for the common

ground.

If an output channel is overloaded, it is switched off for ten seconds until the overload is no

longer present. If the module output range has a total load of more than 8 A, the outputs

are all switched off for 10 seconds and a new test is performed.

Reaction in the Event of a Fault

If the module detects a faulty signal on a digital output, the affected module output is set to

the safe (de-energized) state using the safety switches.

If a fault in the module occurs, all digital outputs are switched off.

In both cases, the module activates the FAULT LED.

The error code allows the user to configure additional fault reactions in the user program.

HIMA DIO 24/16 01 Safety-Related Analog Inputs

Safety Function

The module is equipped with safety-related inputs and outputs.

Safety-Related Analog Inputs

Each group of 8 inputs is provided with a common, short-circuit-proof supply LS+ on the

clamps.

The safety-related application (SIL 3 in accordance with IEC 61508) of the inputs and the

sensors connected must comply with the safety requirements. For more information, refer

to the HIMatrix Safety Manual.

Line Control

The digital outputs DO 1 through DO 8 of the DIO 24/16 01 module can be used to monitor

the own digital inputs or the digital inputs of other modules (e.g., DI 32 01) for short-circuits

and open-circuits, e.g., for an EMERGENCY STOP button complying with Cat. 4 in

accordance with EN 954-1. To this end, the outputs are pulsed and connected to the

safety-related digital inputs. In this case, the outputs assume the function of pulsed outputs.

HIMA DIO 24/16 01 HIMatrix Safety-Related Controller

Product Description

DIO 24/16 01 is a plug-in module for the modular F60 HIMatrix system.

The DIO 24/16 01 module has 24 digital input channels and 16 digital output channels that

are galvanically isolated from the I/O bus. The status of the input and output signals is

displayed by LEDs located on the front plate next to the terminal plugs.

The module can be inserted in the F60 subrack’s slot 3…8 as many times as required. Slots

1 and 2 are reserved for the power supply module and CPU module, respectively.

However, the load on the outputs must not exceed the total current input of the power

supply module.

The module has been certified by the TÜV for safety-related applications up to SIL 3 (IEC

61508. IEC 61511 and IEC 62061), Cat. 4 (EN 954-1) and PL e (EN ISO 13849-1). Further

safety standards, application standards and test standards are specified in the certificate

available on the HIMA website.