Reaction in the Event of a Fault
If the module detects a fault on a digital input, the user program processes a low level in
accordance with the de-energized to trip principle.
The module activates the FAULT LED.
In addition to the channel signal value, the user program must also consider the
corresponding error code.
The error code allows the user to configure additional fault reactions in the user program.
Safety-Related Outputs
Each group of 8 outputs is provided with a connector on the clamps for the common
ground.
If an output channel is overloaded, it is switched off for ten seconds until the overload is no
longer present. If the module output range has a total load of more than 8 A, the outputs
are all switched off for 10 seconds and a new test is performed.
Reaction in the Event of a Fault
If the module detects a faulty signal on a digital output, the affected module output is set to
the safe (de-energized) state using the safety switches.
If a fault in the module occurs, all digital outputs are switched off.
In both cases, the module activates the FAULT LED.
The error code allows the user to configure additional fault reactions in the user program.