Welcome to the official website of CNIACS Automation Technology Co., Ltd!

Fanuc IC660BBA100 Analogue Input/Output Module

Product Description

The IC660BBA100 analogue input/output module is a 115 volt AC from GE Fanuc,

4-input and 2-output analogue block from GE Fanuc. It has a 12-bit resolution, 4 ms update time, and 7 watts of thermal power dissipation. It weighs 4 lbs.

The IC660BBA100 analogue input/output module is part of the GE Fanuc 90-30 series of input/output modules.

It has 4 input circuits and 2 output circuits.

This analogue I/O module with nominal voltage and current offers 5 analogue power ranges: 0 to 10 volts DC,

+/-10 volts dc, +/-5 volts dc, 0 to 5 volts dc, and 4 to 20 mA.

The IC660BBA100 analogue www.cniacs.com input/output block also provides an optional input filter time of up to 1024 milliseconds.

Each output can be left in its final state or at its default value if the communication process is interrupted.

It is backward compatible with its earlier versions, as well as with the GE family of IC697. IC600. and IC550 PLCs.

Replacing the module’s electronics eliminates the need to change the module’s field wiring and configuration.

The IC660BBA100 analogue input/output module has a 12-bit analogue-to-digital converter that converts the input signal current or voltage to a digital value.

The converted signal can be scaled to an integer for representation in engineering units.

The output circuitry is connected to a 12-bit digital-to-analogue converter, which converts the processed value to a voltage or current output signal.

The IC660BBA100 analogue I/O block also automatically calibrates the 2 converters to ensure accurate performance.

It transmits 8 bytes of input data and 4 bytes of output data during each bus scan.

The user can monitor the input and output values in integer form via a handheld monitor.

Connect AC power to terminals 6 and 7 to supply power to the module.

Be sure to connect a 250 volt, 1/8 amp fuse in series with the power connector.

The 2 LED status indicators on the panel show the status of the module.

Fanuc IC200MDD845 Hybrid I/O Module

The allowable voltage range is 0-125 VDC and 0-265 VAC.

The IC200MDD845 has a maximum backplane current consumption of 270 mA, with individual LED status indicators for each input and output channel.

Each input and output channel has a separate LED status indicator that allows local monitoring of the startup and power-up status of each channel of the module.

There is also an OK LED on the module to indicate that backplane power is being continuously supplied to the IC200MDD845.

The IC200MDD845 input channels have an on-state current of 2.0-5.5 mA and an off-state current of 0-0.5 mA.

Conversely, the output load current is 10 mA per point minimum; 2.0 Amperes maximum at 5-265 VAC, 2.0 Amperes maximum at 5-30 VDC, and 2.0 Amperes maximum at 5-30 VDC.

2.0 Amperes at 5-30 VDC, and 0.2 Amperes at 31-125 VDC, all with resistive loads.

Typical response times for the input and output www.cniacs.com channels are 0.5 milliseconds for on signal transitions and 10 milliseconds for off signal transitions, respectively.

The GE Fanuc IC200MDD845 hybrid module is a GE Fanuc product that is part of the VersaMax family.

The module supports discrete inputs and outputs, providing two sets of eight inputs each and another set of eight outputs for a total of 24 points.

The IC200MDD845 module has A-type relay outputs that are individually isolated.

The GE Fanuc IC200MDD845 module requires an IC200CHS series carrier base. It supports interchannel isolation of output points only.

It does not support buffers, internal fuses, or any other protection system. There are multiple LEDs to indicate the status of the device.

The IC200MDD845 hybrid module is powered from the backplane, but a second power supply is required for any additional loads.

The total amount of power the module draws from the backplane power supply depends on the number of active I/O points, with a maximum total current draw of 270 mA.

The total number of I/O points that can be active at the same time depends on a number of factors. the IC200MDD845 Hybrid Module has an input point voltage of 24 volts DC and an output voltage range of 0 to 125 volts.

The IC200MDD845 hybrid module has an input point voltage of 24 volts DC and an output voltage range of 0 to 125 volts DC and 0 to 265 volts AC at 47 to 63 Hz. 1.

ABB New VD4 Medium Voltage Vacuum Circuit Breaker

Overview of the new VD4 Medium Voltage Circuit Breaker

The new VD4 Medium Voltage Circuit Breaker is the perfect combination of vacuum interrupter design and manufacturing technology with resin-embedded pole plates and technical excellence in circuit breaker design, engineering and production.

The VD4 medium voltage circuit breaker uses vacuum interrupters embedded in resin pole plates.

Embedding the interrupters in resin poles makes the circuit breaker poles particularly robust and protects the interrupters from shock, dust build-up and moisture.

A vacuum interrupter consists of a contact and an interrupting chamber.

Vacuum interrupters Vacuum circuit breakers do not require an interrupting and insulating medium. In fact, the interrupter chamber contains no ionisable material.

In any case, the arc generated when the contacts separate consists entirely of melted and vapourised contact material.

The arc is supported by external energy until the current disappears near its natural zero point.

At this point, the load density decreases rapidly and the metal vapour condenses rapidly, leading to an extremely rapid recovery of the dielectric properties.

The vacuum interrupter thus regains its insulating capacity and its ability to withstand transient recovery voltages, and the arc is finally extinguished.

Due to the high dielectric strength achieved in a vacuum even at short distances, circuit interruption is guaranteed when the contacts separate a few milliseconds before the current passes through the natural zero point.

The special geometry of the contacts and the materials used, as well as the limited duration of the arc and the low voltage

guarantees minimum wear and a long service life of the contacts. In addition, the vacuum prevents oxidation and contamination of the contacts.

Structure

The operating mechanism and the magnetic poles are fixed to a metal frame which also serves as a support for the fixed circuit breakers.

The compact construction ensures robustness and mechanical reliability.

In addition to isolating contacts for connecting auxiliary circuits and flexible cables with plugs, the

The tractable circuit breakers are also equipped with a www.cniacs.com bracket trolley for putting them into or taking them out of the switchgear or enclosure with the door closed.

– Vacuum interrupter technology

– Vacuum contacts protect against oxidation and contamination

– Vacuum interrupters embedded in resin poles

– The interrupters are protected against vibration, dust and humidity.

– Poles sealed for life

– Operation in different climatic conditions

– Limited switching energy

– Energy storage operating mechanism with anti-pumping device as standard

– Simple customisation with a full range of accessories

– Fixed and withdrawable

– Compact dimensions

– Compact dimensions Robust and reliable

– Limited maintenance

– Doors closed when circuit breakers are racked in and out

– Special locks on the operating mechanism and forklift truck prevent incorrect and dangerous operation

– High environmental compatibility

ABB VD4 Medium Voltage Vacuum Circuit Breakers Quenching Principle for Arc Extinguishing Chambers

Spiral geometry of ABB vacuum interrupter contacts

The special geometry of the helical contact generates a radial magnetic field in all areas of the arc column and concentrates it around the circumference of the contact.

Spontaneously generated electromagnetic forces acting in a tangential direction cause the arc to rotate rapidly around the contact axis.

This means that the arc is forced to rotate and involves a wider surface than a fixed contracting arc.

All this makes contact erosion negligible, except for minimising thermal stresses on the contacts.

Most importantly, the arc extinguishing process can be controlled even in the case of extremely high short circuits.

ABB vacuum interrupters are zero-current interrupters, www.cniacs.com which do not produce any re-strikes.

At zero current, the current charge is rapidly reduced and the metal vapour condenses, thus restoring the maximum dielectric strength between the interrupter contacts in microseconds.

VD4 circuit breakers have passed the following tests to ensure the safety and reliability of the equipment when used in any installation environment.

– Type tests: heating, industrial frequency withstand voltage insulation, lightning impulse withstand voltage insulation, short-time and peak withstand voltage current,

Mechanical life, short-circuit current generation and breaking capacity, no-load cable disconnection.

– Individual tests: main circuit insulation at working frequency voltage, insulation of auxiliary circuits and operating mechanisms, main circuit resistance measurement, mechanical and electrical operation.

Service safety

With a full range of mechanical and electrical locks (available on request), it is possible to build safe distribution switchgear with VD4 circuit breakers.

Locking devices have been studied to prevent incorrect operation and to check the device while maximising operator safety.

Keyed locking or padlocking devices enable switching and/or racking-in and racking-out operations.

Racking out with door closed devices allow the circuit breaker to be racked in or out of the switchgear only when the door is closed.

Anti-breaking locks prevent breaking in of circuit breakers with different current ratings, as well as breaking in operations when the breaker is closed.

ACCESSORIES

VD4 circuit breakers are available with a comprehensive range of accessories to meet all installation requirements.

The operating mechanism has a standardised range of accessories and spare parts which are easy to identify and order.

The accessories can be easily fitted from the front of the circuit breaker. Electrical connections are made using plug and socket connectors.

The equipment is simple to use, maintain and service with limited resource requirements.

Operating Mechanism

The operating mechanism of the VD4 circuit breaker is designed to be simple and easy to use, with a wide range of customised accessories for quick and easy installation.

This simplicity gives the equipment a higher degree of reliability.

The operating mechanism is of the energy storage type and is fitted as standard with an anti-pumping device with appropriate locks to prevent incorrect operation.

Each operating sequence can only be activated if all the conditions to ensure its correct execution are met.

All types of VD4 circuit breakers have the same accessories.

– Highly reliable operating mechanism thanks to low component count due to mass-produced system

– Extremely easy to maintain

– The accessories are common to the entire series and are the same for both AC and DC applications

– Quick and easy installation or replacement of electrical accessories, as the cables are already equipped with plug and socket connectors

– Mechanical anti-pumping device as standard

– Built-in closing spring-loaded charging lever

– Protective cover for the opening and closing buttons that can be operated with special tools

– Padlock device on the operating buttons

ABB SPAM150C Motor Protection Relay

Brief Introduction

The SPAM150C Motor Protection Relay is a general purpose combination relay designed primarily for the protection of AC motors for a variety of applications.

It combines a large number of protection functions in one unit. The relay provides a complete set of protection against motor damage caused by various electrical faults.

The relay is also suitable for other equipment requiring thermal overload protection, such as cable or power transformer feeders.

Summary of Protection Functions

The relay thermal overload unit protects the motor against short- and long-term overloads. The maximum permissible continuous load depends on the setting value 1.

Normally this setting value is taken as the rated full www.cniacs.com load current (FLC) of the motor at an ambient temperature of 40°C. The motor can be overloaded for a short period of time if the motor is not loaded.

When the motor current increases to 1.05I under the above conditions, the thermal overload unit starts after a certain delay.

If the ambient temperature of the motor is below 40°C for a long period of time, the setting value I. can be set to .05…1.10 times the full load current (FLC) of the motor. 1.10 times.

The short-time overload phenomenon mainly occurs during the starting process of the motor. The motor is normally allowed to start twice under cold conditions and once under hot conditions.

One start is permitted under hot conditions, therefore, depending on the starting time of the motor, an integrating value t determining the characteristics of the thermal overload unit can be derived.

This value can be easily determined from the time/current graph in the hot state. t curve is selected from the starting current versus the corresponding starting time (with an appropriate margin).

The t-curve is selected from the starting current versus the corresponding starting time (with an appropriate margin). Using the same value of t, the total permissible starting time of the motor under cold conditions can be found from the cold curve.

ABB SPAJ140C Combined overcurrent and earth fault relay

Function

– Three-phase, low-setting phase overcurrent device with timed or inverse definite minimum time (IDMT ) characteristics

– Three-phase, high setting phase overcurrent device with instantaneous or timed characteristics

Operation

– Low-level ground fault device with timed or inverse deterministic minimum time (IDMT) characteristics

– High-level ground-fault unit with instantaneous or definite-time operation

– Built-in circuit breaker fault protection

– Two heavy load relays and four signal output relays

– Matrix of output relays for routing the start or trip signals of the protection stage to the desired output relays

– Local display of measured values, set values and data recorded during faults

– Reading and writing of set values via local display and front panel pushbuttons or via the serial interface and fiber optic bus of the higher-level system

– Self-monitoring system for continuous monitoring of electronics and microprocessor operation

Microprocessor operation

– Powerful software support for relay parameterization, reading of measured and logged values, events, etc., and

Powerful software support for relay parameterization, reading of measured and recorded values, events, etc., and storage of readings

– Member of the SPACOM product family and ABB’s distribution automation system

– CE marking according to the EU EMC directive

APPLICATIONS

The SPAJ 140 C combined overcurrent and earth fault relay is intended for use on solid earths,

The combined overcurrent and earth fault relay www.cniacs.com is used for selective short-circuit and earth fault protection of radial feeders in solidly earthed, resistance earthed or impedance earthed power systems.

The integrated relay consists of an overcurrent unit and an earth fault unit with flexible tripping and signaling facilities.

The overcurrent and earth fault relays can also be used for other applications where single, two or three phase overcurrent protection is required.

The SPAJ 140 C combined overcurrent and earth fault relay is part of ABB’s distribution automation concept, a complete solution for controlling and managing power systems.

ABB SPAD346C Integrated Differential Relay

Features

Integrated three-phase differential relay, overcurrent relay and earth fault relay

Stabilized three-phase differential relays provide winding short-circuit and turn-to-turn fault protection for two-winding transformers and generator-transformer units, and winding short-circuit protection for generators.

Earth fault protection for transformer windings on the HV and LV side according to the required principle:

Stabilized differential current principle, high impedance principle, calculated or measured residual current principle or neutral current principle

Three-stage overcurrent protection for transformer and generator as well as two-stage backup protection for earth fault protection.

Differential relays with operating characteristics that can be easily adapted to different applications Short operating times, stable operation even in the event of partial saturation of the current transformer.

Prevents unwanted operation in the event of faults and transformer inrush currents outside the protective field.

Blocking based on the ratio of the second harmonic to the fundamental component of the differential current prevents unwanted operation in the event of transformer inrush currents.

Blocking based on the ratio of the fifth harmonic www.cniacs.com to the fundamental component of the differential current prevents unwanted operation in the event of transformer overexcitation.

– If the ratio of the fifth harmonic to the fundamental component of the differential current increases at high overvoltages, this blocking condition can be eliminated

Double-winding transformer protection without transformers – digital vector group matching on HV and LV side

Wide range of CT ratio corrections – precise corrections via digital settings Sensitive phase current and phase angle displays for easy checking of measurement circuits

Emerson DeltaV Distributed Control System Power Modules

Ease of use

Increased usability

Flexible and cost-effective

Small footprint

Introduction

Power – without it, your system would not function. www.cniacs.com deltaV™ high-capacity power supplies provide you with the most efficient and reliable power solutions available.

DeltaV high-capacity power supply kits power system electronics and ffeld. This is all the power you need for your DeltaV system.

Benefits

Easy to use. DeltaV High Capacity Power Supplies provide reliable 12 V and 24 VDC power for DeltaV system power and bus ffeld power needs.

They mount easily on T-shaped DIN rails!

Increased availability. Redundant modules based on active MOSFET technology offer higher efficiency and lower voltage drop than conventional diode modules, resulting in less heat dissipation and higher system reliability.

Flexible and Cost-Effective DeltaV Bulk power supplies are flexible and cost-effective to use because of the ability to utilize external redundant modules, for example, if load sharing is required.

For example, if load sharing is required.

Models are available with and without conformal coating.

Small footprint DeltaV Bulk Power Supplies have a small, competitive footprint!

Emerson DeltaV Network Smart Switches

Benefits

Plug-and-play installation. Smart Switches feature a DeltaV-compatible setup that installs into the DeltaV network right out of the box.

They require no user configuration to fully support DeltaV network communications. In addition

The default configuration cannot be changed by the user, so you don’t have to worry about installing an incorrectly configured switch.

Automatic lockout prevents unauthorized network connections – Disabling unused network connections is a “best security practice” that helps you comply with plant security policies.

Disabling unused network connections is a “best security practice” that helps you comply with factory security policies.

With the switch’s built-in one-click lockout feature, you can automatically lock out all unused network ports on your system with the click of a button in the DeltaV application.

Full range of switch hardware configurations.

DeltaV network switches are available in a variety of hardware solutions. From 24-port rackmount units to fixed-port and modular field-installable switches.

DeltaV network switches are available to meet a variety of network requirements.

These switches are all you need to implement a DeltaV network.

DeltaV network switches replace currently supported Cisco and Hirschmann switches for implementing DeltaV control networks.

The VE6046. VE6047. and VE6048 DeltaV Smart switches www.cniacs.com can be used in applications that previously used Cisco switches.

The VE6041. VE6042. and VE6043 Smart Switches can be used in any application where DIN rail field mounting of switches is required.

In most cases, DeltaV network switches are a direct replacement for our existing supported managed switches.

Fully supported by Emerson. As an Emerson product, these DeltaV network switches are fully supported by Emerson.

Fully supported by Emerson. You can get full technical support, warranty support, product support, and education from our global service centers.

All provided by Emerson. In the unlikely event that your switch fails, smart switches are also included in the Rapid Module Replacement Program, so you can get a replacement quickly.

Emerson DeltaV™ Redundant Controller

Uninterrupted control operation

Online upgradeable

Automatic commissioning

Bumperless transition

Introduction

Now you don’t have to worry about controller hardware failures interrupting your process and causing costly downtime.

With redundant controllers, your processes are automatically protected in the event of a hardware failure.

If the active controller fails, the backup controller automatically takes over, providing uninterrupted control operation without initialization or user intervention.

Switchover does not cause any interference with the ffeld output signals, so your process can continue to run uninterrupted.

Adding redundancy requires no special wiring or configuration; simply add a controller to your existing hardware.

Redundant controllers also support online upgrades of controller software and hardware. So you can upgrade MD Plus to MQ or MX online, or SD Plus to SQ online.

or SD Plus to an SQ or SX controller online without changing the configuration.

Benefits

Uninterrupted control operation. By installing redundant M-Series, S-Series, and PK controllers, you create a “safety net” that

protects your process from unexpected controller failures. In the event of a hardware failure, a backup controller is always available to keep your control and process up and running.

Online upgrades. Installing a redundant DeltaV www.cniacs.com controller allows you to upgrade your DeltaV system online.

New software can be installed into the backup controller online without disrupting operations.

Once the upgrade is complete, the backup controller is automatically configured and available, allowing you to switch to the new ffrmware without interrupting your process.

Once the switchover is complete, the original active controller can be upgraded. In addition, MQ controllers can be upgraded online to MX controllers.

SQ controllers can be upgraded online to SX controllers. This ensures that your system is always ready to expand as your control strategy evolves.

Automatic commissioning. The system automatically detects, commissions, and downloads spare controllers so you can safely replace equipment.

Add redundancy online by simply installing a new 2-wide backplane with system power and MQ, MX, SQ or SX controllers.

The SZ Controller Carrier or Dual Universal Safety Carrier provides 2 slots for SZ controllers, so there is no need to add anything other than additional SZ controllers.

PK controller carriers also provide 2 slots, so simply add a PK controller to an existing carrier.

The engineering database is automatically updated and the spare controller can be activated by simply assigning and downloading a controller redundancy license, all without interrupting the process.

There are no dip switches, jumpers or addresses to assign. The backup controller automatically assigns the proper backup address and starts working, protecting your process.

Bufferless Transitions The DeltaV controller is designed for bufferless control transitions from the active controller to the standby controller.

During this time, the output channels maintain their output state until the switchover is complete and the control module begins execution.

The control module uses signal status to ensure that all I/O channels are normal before taking control action on them.

All output signals are synchronized via the I/O readback function to ensure that control calculations are made based on the current output state.

When using CHARM or DeltaV Classic I/O cards with or without Foundation™ ffeldbus devices.

This ensures an uninterrupted transfer of control during switchover.

Search for products

Back to Top
Product has been added to your cart