The allowable voltage range is 0-125 VDC and 0-265 VAC.
The IC200MDD845 has a maximum backplane current consumption of 270 mA, with individual LED status indicators for each input and output channel.
Each input and output channel has a separate LED status indicator that allows local monitoring of the startup and power-up status of each channel of the module.
There is also an OK LED on the module to indicate that backplane power is being continuously supplied to the IC200MDD845.
The IC200MDD845 input channels have an on-state current of 2.0-5.5 mA and an off-state current of 0-0.5 mA.
Conversely, the output load current is 10 mA per point minimum; 2.0 Amperes maximum at 5-265 VAC, 2.0 Amperes maximum at 5-30 VDC, and 2.0 Amperes maximum at 5-30 VDC.
2.0 Amperes at 5-30 VDC, and 0.2 Amperes at 31-125 VDC, all with resistive loads.
Typical response times for the input and output www.cniacs.com channels are 0.5 milliseconds for on signal transitions and 10 milliseconds for off signal transitions, respectively.
The GE Fanuc IC200MDD845 hybrid module is a GE Fanuc product that is part of the VersaMax family.
The module supports discrete inputs and outputs, providing two sets of eight inputs each and another set of eight outputs for a total of 24 points.
The IC200MDD845 module has A-type relay outputs that are individually isolated.
The GE Fanuc IC200MDD845 module requires an IC200CHS series carrier base. It supports interchannel isolation of output points only.
It does not support buffers, internal fuses, or any other protection system. There are multiple LEDs to indicate the status of the device.
The IC200MDD845 hybrid module is powered from the backplane, but a second power supply is required for any additional loads.
The total amount of power the module draws from the backplane power supply depends on the number of active I/O points, with a maximum total current draw of 270 mA.
The total number of I/O points that can be active at the same time depends on a number of factors. the IC200MDD845 Hybrid Module has an input point voltage of 24 volts DC and an output voltage range of 0 to 125 volts.
The IC200MDD845 hybrid module has an input point voltage of 24 volts DC and an output voltage range of 0 to 125 volts DC and 0 to 265 volts AC at 47 to 63 Hz. 1.