Welcome to the official website of CNIACS Automation Technology Co., Ltd!

Woodward MicroNet TMR® Control System Programming

Programming

The MicroNet TMR control system provides an

IEC1131-3 environment for programming. Application

code is generated by use of Woodward’s GAP™

Graphical Application Programming environment or

Woodward’s Ladder Logic programming environment.

• Function Block Programming — through Woodward GAP

• Sequential Function Chart Programming — through

Woodward GAP

• Ladder Logic Programming — through Woodward

Ladder Logic Programmer

The MicroNet TMR operating system, together with

GAP, produces a very powerful control environment

designed for control and protection of turbines and

compressors. Woodward’s unique scan rate structure

ensures that control functions will execute

deterministically at defined scan rates, with critical

control loops able to be processed within 5 milliseconds.

Accurate speed and speed acceleration and

deceleration rates are sensed using a sampling rate of

100 microseconds. These ultra-fast sampling and

response rates allow the controller to adequately

respond to system transients, failures, or safety events.

Woodward MicroNet TMR® Control System Fault Tolerance

Fault Tolerance

Each of the MicroNet TMR controller’s kernel sections

individually monitors all input data, performs all

application calculations, and generates all output values

and responses. This control’s architecture allows it to

operate with any single point of failure, without shutting

down. Architected for reliability and safety, the system’s

CPU fault tolerance logic of 3-2-0 allows the control to

function normally with any CPU module failed or

removed, and ensures a safe shutdown with multiple

CPU failures. An analog I/O fault tolerance logic of 3-2

1-0 allows the control to function normally with any one

or two analog modules failed or removed. A discrete I/O

fault tolerance logic of 3-2-1-0 allows the control to

function normally with any one or two discrete modules

failed or removed. A power supply fault tolerance logic of

2-1-0 allows the control to function normally with any one

power supply failed or removed.

Each kernel CPU module runs the identical software

program, in “lock-step” with the other two CPUs. All

inputs from each kernel are distributed to the other two

kernels. For each sensed input, each CPU compares its

read value with the value the other two CPUs read

before outputting a signal to the application software. All

CPUs use the same voted input signals in the same

application calculations to generate the same outputs.

All output values are then exchanged between kernels,

the results are voted, and the appropriate value is output.

Woodward MicroNet TMR® Control System features include

MicroNet TMR features include:

IEC61508 SIL-3 certified

Network-safe CPUs

Simplex or redundant CPU configurations

VME-based (full and narrow chassis)

Real-time multitasking VxWorks® operating system

Woodward’s proven Graphical Application Programmer (GAP) software and support tools

Deterministic update rates as fast as 5 milliseconds

Improves control system availability and reliability

SNTP-compliant for time synchronization

Expandable with redundant real-time networks in CAT-5 or fiber optic configurations

Ethernet communications

Simplex or dual power

Modular I/O

Events are timestamped to 1 millisecond

Hot-swap modules for in-line maintenance

MicroNet TMR features include:

Speed and load control

Temperature and process control

Combustion control

Anti-surge control

System sequencing and package assist control

Tight load rejection performance

Sophisticated DLE fuel control algorithms

Initial surge detection

Long-term naval program

Alarm + shutdown communicationsWoodward MicroNet TMR® Control System

Woodward MicroNet TMR® Control System features

Available inputs and outputs include

 Magnetic pickups (MPUs) and proximity probes

 Discrete I/O

 Analog inputs/outputs

 Thermocouple inputs

 Resistance Temperature Devices (RTD)

 Proportional and integrated actuator drives (integrated AC and DC position inputs)

 Ethernet and serial communications

 Distributed analog, discrete, thermocouple and RTD I/O available with LinkNet HT

Woodward’s MicroNet TMR (Triple Modular Redundancy) controller is a customizable digital control

platform that reliably controls and protects steam, gas turbine and compressor trains.

These are system-critical applications where safety issues can arise or cause significant economic loss.

Operating Conditions:

Temperature (0 to 55) °C / (32 to 131) °F Ambient Air Temperature Range

Shock US MIL-STD-810C, Method 516.2-1. Procedure 1B

Vibration Lloyd’s ENV2 Test #1

Emissions * EN61000-6-4

Immunity * EN61000-6-2

Achilles Level 1 Certification

Certifications * CE, UL/cUL, CSA (Class I, Zone 2), LR for ENV1 and ENV2. ABS, GOST

Other international compliance (using MicroNet safety modules) TÜV certified to IEC 61508 Part 1-7.

Functional Safety of Electrical/Electronic/Programmable Systems, Electronic Safety-Related Systems

Woodward MicroNet TMR® Control System utilizes

These specialized modules can time stamp discrete events in 1 millisecond and analog events in 5 milliseconds.

The MicroNet TMR® utilizes two power supplies, each supplying power to the controller from a separate power source.

Within each power supply are three independent power converters, one each for the CPU and I/O sections.

This triple power supply structure provides maximum protection against single or multiple points of hardware failure.

The controller’s dedicated TMR® Discrete I/O Module is designed for critical discrete circuits.

The module accepts discrete inputs and distributes them to each individual core section,

as well as outputs relay contacts to drive discrete application logic.

The module’s special TMR® outputs utilize a six-relay configuration and integrated potential fault detection

logic that allows any one or two relays to fail without affecting the integrity of the output contacts.

This configuration allows routine relay testing and in-circuit repair without compromising output or system integrity.

Woodward MicroNet TMR® Control System Description

Description

The MicroNet TMR® control platform features a ruggedized rackmount chassis

with in-line replaceable I/O modules and triple modular architecture for 99.999% availability.

This triple modular redundancy-based system consists of three independent cores (A, B, and C) housed in the platform’s compact chassis.

Each core section includes its own CPU, CPU power supply, and up to four I/O modules,

which can be used for simplex I/O, redundant I/O, triple redundant I/O, or any combination of redundancy.

I/O can be expanded via a system expansion chassis or the ruggedized LinkNet HT Distributed I/O.

The platform’s high-density modules and integrated application software reduce

troubleshooting time by providing first-out indication of monitored system events.

Designed from the ground up as a turbine control system, the MicroNet TMR® controller’s actuator

drive module is available with the use of single or dual redundant coils,

Proportional or integral turbine valve servos with AC or DC feedback position sensors using single or dual redundant coils.

The MicroNet TMR® controller can accommodate any combination of Woodward MicroNet I/O modules and LinkNet HT

distributed I/O to provide maximum application flexibility.

Woodward 2301A Electronic Load Sharing and Speed Control

Description

The 9905/9907 series of the Woodward 2301A controls load sharing and speed of generators driven by diesel or gasoline engines, or steam or gas turbines. 

These power sources are referred to as “prime movers” throughout this manual.

The control is housed in a sheet-metal chassis and consists of a single printed circuit board. All potentiometers are accessible from the front of the chassis.

The 2301A provides control www.cniacs.com in either isochronous or droop mode.

The isochronous mode is used for constant prime mover speed with:

 Single-prime-mover operation;

 Two or more prime movers controlled by Woodward load sharing control systems on an isolated bus;

 Base loading against an infinite bus with the load controlled by an Automatic Power Transfer and Load (APTL) Control, an Import/Export Control, a Generator Loading Control, a Process Control, or another load-controlling accessory.

The droop mode is used for speed control as a function of load with:

 Single-prime-mover operation on an infinite bus or

 Parallel operation of two or more prime movers.

The following is an example of the typical hardware needed for the 2301A system controlling a single prime-mover and generator:

 A 2301A electronic control

 An external 20 to 40 Vdc power source for low-voltage models; 90 to 150 Vdc or 88 to 132 Vac for high-voltage models

 A proportional actuator to position the fuel-metering device 

 Current and potential transformers for measuring the load carried by the generator.

Applications

The 2301A 9905/9907 series electronic controls have switch-electable speed ranges. Any of these control models can be set to operate within one of the following rated speed ranges:

 500 to 1500 Hz

 1000 to 3000 Hz

 2000 to 6000 Hz

 4000 to 12 000 Hz

Woodward CPC-II Electrohydraulic Current Pressure Converter

Features

 Actuators and self-cleaning valves are 4 times stronger with ‘sludge buster’ technology

 Patent-pending ‘Sludge Buster’ cleaning technology

 Advanced control algorithms and diagnostics

 Redundant optimum control configuration

 Same mounting base footprint as the CPC*

 Enhanced feature benefits:

 Removes 40 μm size dirt and reduces or eliminates filter/screen service work

 Removes sludge build-up without compromising operational integrity

 Industry-leading stability and buffer-free, precise throttle control

 Configuration flexibility to meet your system needs

 Easily upgrade your existing CPC* or Voith E360 I/H

CPC-II Upgrade Programme

(Current Pressure Converter, Generation II)

Maximise uptime with Woodward’s Dirt Buster www.cniacs.com technology Upgrade with Woodward’s CPC-II Electrohydraulic Current Pressure Converter

your Woodward CPC* or Voith E360 I/H throttle controller.

The CPC-II solves the turbine market’s number one reliability problem: oil contamination.

CPC-II:

 removes 40 μm sized dirt, reducing or even eliminating turbine control filter maintenance altogether!

 removes sludge build-up without compromising operational integrity

 features industry-leading stability and snubberless precision throttle control

 Easily upgrades existing CPC or Voith converters

The power of the CPC-II is combined with Woodward’s industry-leading control point algorithms, advanced diagnostics and PC-based service tools.

This powerful solution provides stable control during normal turbine operation and trouble-free control in the event of a plant failure.

By minimising process overshoot or undershoot conditions, you can maximise uptime and increase productivity.

Woodward 8256-008 Electric Governor (EPG)

Product Description

Part of the Woodward Electric Governor Series is the actuator model 8256-008.This is a speed control system that is compatible with a variety of engines.

This model can be used on gas, petrol or diesel www.cniacs.com engines. The product rotates clockwise to ensure the most efficient use of fuel.

To use the Model 8256-008 actuator, the engine’s speed control must be compatible with the system.

It is powered by a 24V battery and weighs just over a pound. The supply voltage for this model is a minimum of 10 Vdc and a maximum of 16 Vdc.

The Model 8256-008 has a maximum power consumption of 60 watts. It is also equipped with an overtravel feature

The ambient temperature around this EPG should be maintained between -40 and 200 degrees Fahrenheit.

Mounting of this product must be done on sheet metal and should be done with torque screws.

This Woodward model is constructed from corrosion-resistant materials to ensure a longer product life.

The EPG 8256-008 model can be operated in single phase step-down control and will then share the load when operated in step-down mode.

Woodward 2301E Digital Load Sharing and Speed Controller

The 2301E provides load distribution and speed control for generators driven by diesel or gas engines.

Using the built-in flexible configuration software, application variants can now be selected using an external computer (PC).

Changing the application www.cniacs.com to suit the engine speed range, gear teeth and selecting forward or reverse action is just a software setup away.

The 2301E controller is backward compatible with the existing 2301D product as it has the same footprint and mounting configuration.

The new controller ensures the continued availability of a proven and versatile product with enhanced features:

-Separate RS-232 and RS-422 serial ports, both with 9-pin connectors

-Additional status LEDs for power and RS-422 communication

-Failure data logging feature that collects 16 seconds of data every 10 milliseconds during shutdown, peak speed, and load detection events

-Low current PWM output for driving Woodward L-Series, F-Series, P-Series and PISC actuators

-New terminal block accommodates additional I/O, with most terminals located in the same location as the 2301D model.

-Major compliance approvals

-Engine/generator or pump applications

-Multiple dynamics

-Manifold Air Pressure (MAP) limiter

-Torque limiter

-Low speed sensing capability

-Remote speed and load reference

-Soft load transfer

-Automatic idle to rated switching

-Load dump/load pulse option

-Idle down function

-Optional Modbus® serial communication

-Adaptive speed sensing algorithm

-Two serial ports

-Data logging function

-2301E ToolKit service tool or Control Assistant programmable

-Common or hazardous location chassis

Replacements:

8273-1012 is a direct replacement for 8273-139 and 8273-141

The Woodward 2301E microprocessor-based controller has the same functionality as the 2301A Load Sharing and Speed Controller and the 2301D Load Sharing and Speed Controller.

The control unit is housed in a sheet metal enclosure for general and hazardous locations and consists of a single printed circuit board.

The 2301E is configured using a computer equipped with Control Assistant software or the Woodward ToolKit service tool.

The computer is connected to the 2301E via a 9-pin connector (RS-232 port). Modbus control is available through a second serial port (RS-422).

The controller is powered by a 24 Vdc power supply.

The 2301E includes

 1 load cell circuit

 1 actuator driver, 4-20 mA, 0-20 mA, 0-200 mA or PWM

 1 MPU speed sensor

 1 configurable analogue output

 2 configurable analogue inputs

 8 discrete (switching) inputs

 4 discrete (relay driver) outputs

The 2301E has an operating temperature range of -40 to +70 °C (-40 to +158 °F).