Woodward will provide update files for legacy DSLC-2 and MSLC-2 devices Schedule

The important control functions run on the same task rates that ensures the same control dynamic.

Most important, it is being designed to be able to run with the legacy DSLC-2/MSLC-2 system.

This becomes more important than ever due to lack of obtainable components that may

force us to make a hard stop to the DSLC-2/MSLC-2 product line later this year.

If some minor rules are observed the DSLC-2XT can be mixed with already existing DSLC-2 / MSLC-2 in an application.

MSLC-2XT (in line with DSLC-2XT) is also in preparation and comes few months after DSLC-2XT.

Others:

The communication 9-pin D-sub connectors are replaced by phoenix plugs with screw terminals

The analog outputs 1 & 2 are supported with two terminals now (the shunt for voltage output is internally populated)

Schedule:

DSLC-2XT: Design release to production scheduled for Sept’22.

Shipment expected Oct’22 however depends on availability of components.

Limited early sample and draft manual available. Please contact your account manager.

MSLC-2XT: Design release to production scheduled for Nov’22.

Shipment expected Dec’22 however depends on availability of components.

Limited early sample and draft manual available. Please contact your account manager.

Part Numbers:

8440-2298: MSLC-2XT

8440-2299: DSLC-2XT

Woodward Communicating with legacy DSLC-2 (and MSLC-2) General

General:

The DSLC-2XT/MSLC-2XT is an upward compatible successor device for the DSLC-2/MSLC-2.

They are based on the easYgen-3400XT-P2 hardware. It is designed to function

as good as the original DSLC2/MSLC-2 (version 1.1511).

The new generation is equipped with a more powerful CPU, memory, and communication.

It is more responsive in HMI and SCADA communications.

The important control functions run on the same task rates that ensures the same control dynamic.

Most important, it is being designed to be able to run with the legacy DSLC-2/MSLC-2 system.

This becomes more important than ever due to lack of obtainable components that may

force us to make a hard stop to the DSLC-2/MSLC-2 product line later this year.

If some minor rules are observed the DSLC-2XT can be mixed with already existing DSLC-2 / MSLC-2 in an application.

MSLC-2XT (in line with DSLC-2XT) is also in preparation and comes few months after DSLC-2XT.

Others:

The communication 9-pin D-sub connectors are replaced by phoenix plugs with screw terminals

The analog outputs 1 & 2 are supported with two terminals now (the shunt for voltage output is internally populated)

Woodward Communicating with legacy DSLC-2 (and MSLC-2)

Important Considerations:

Communicating with legacy DSLC-2 (and MSLC-2)

Woodward will provide update files for legacy DSLC-2 and MSLC-2 devices in the field if

there is to run a mix of both DSLC-2/MSLC-2 generations.

The legacy device will then send their UDP messages in a way that DSLC-2XT/MSLC-2XT can evaluate.

It is mandatory to load this update file into the legacy devices for the system to run smoothly.

2. Using your existing settings file (*. WSET) from legacy DSLC-2 (and MSLC-2)

Woodward will provide a conversion rule for ToolKit to make the configuration transfer as smooth as possible.

Some minor parameters will be shown in a log file, to be evaluated manually.

3. The AC measurement of the DSLC-2XT (and MSLC-2XT)

The measurement hardware and software are different in comparison to the legacy devices.

This is mainly due to higher accuracy, more flexible measurement range and fast response characteristics.

The earthing of the DSLC-2XT/MSLC-2XT devices has become more important due to higher impedance of the measurement circuits.

4.ToolKit

To give you a seamless transition experience, the ToolKit layout (*. WTOOL file) is designed like the original devices.

There are few less parameters due to new AC measurement and communication interfaces.

5.Documentation server

Product literature (manuals, config. files, software etc.) is hosted on a documentation server

that is easily accessible by a QR code printed on the housing.

Two additional QR stickers are delivered with the controllers to help you paste them at a location convenient to you.

Subsequently, product CD is removed from scope of delivery.

What are the differences between DSLC-2 MSLC-2 and DSLC-2XT MSLC-2XT ?

Woodward understands the time-intensive nature of Power Generation projects.

Ensuring the longevity of our products is one way we make our customers successful.

Woodward has supplied and supported the field proven MSLC-2/DSLC-2 line of

synchronizers and load controllers for over a decade.

An upcoming state of the art Drop-In replacement successor extends the life cycle of this product line for another decade and

possibly beyond. This document provides an overview of what to expect from the successor products,

namely MSLC-2XT/DSLC-2XT respectively.

Important Features:

→  Drop-In Replacement (Mounting dimensions and overall dimensions are same)

→  Similar Look and Feel as MSLC-2/DSLC-2 (available in back panel mounting style)

→  USB Connectivity to PC (RS-232 port is removed; new: USB Type B)

→  Direct connect up to 690VAC (increased range handled by device configuration)

→  Software selectable 1A/5A CT input (supported by one P/N)

Woodward MSLC-2™ Master Synchronizer and Load Control SPECIFICATIONS

SPECIFICATIONS

Power supply …………………………………………………. 12/24 Vdc (8 to 40 Vdc)

Intrinsic consumption ………………………………………………………… max. 15 W

Ambient temperature (operation) ………………. -40°C to 70°C / -40 to 158°F

Ambient temperature (storage) …………………. -40°C to 85°C / -40 to 185°F

Ambient humidity……………………………………………… 95 %, non-condensing

Voltage …………………………………………………………………………………… ( /)

120 Vac [1] Rated (Vrated) …………………………………….. 69/120 Vac

Max. value (Vmax) …………………………………….. 86/150 Vac

Rated voltage phase – ground …………………………………………. 150 Vac

Rated surge volt. (Vsurge) ……………………………………………. 2.5 kV

and 480 Vac [4] Rated (Vrated) …………………………………… 277/480 Vac

Max. value (Vmax) …………………………………… 346/600 Vac

Rated voltage phase – ground …………………………………………. 300 Vac

Rated surge volt. (Vsurge) ……………………………………………. 4.0 kV

Accuracy …………………………………………………………………………… Class 0.5

Measurable alternator windings ……………………… 3p-3w, 3p-4w, 3p-4w OD

Setting range ………………… primary ……………………………50 to 650.000 Vac

Linear measuring range …………………………………………………….. 1.25×Vrated

Measuring frequency……………………………………….. 50/60 Hz (40 to 85 Hz)

High Impedance Input; Resistance per path ……. [1] 0.498 M, [4] 2.0 M

Max. power consumption per path ………………………………………… < 0.15 W

Current (galvanically isolated) Rated (Irated) …………. [1] ../1 A or [5] ../5 A

Linear measuring range ……………………………………………….. Igen = 3.0×Irated

Imains/ground = 1.5×Irated

Setting range ……………………………………………………………….. 1 to 32.000 A

Burden ……………………………………………………………………………… < 0.15 VA

Rated short-time current (1 s) ……………………………[1] 50×Irated, [5] 10×Irated

Accuracy …………………………………………………………………………… Class 0.5

Power …………………………………………………………………………………………….

Setting range…………………………………………………. 0.0 to 999.999.9 MW/kvar

Discrete inputs …………………………………………………….. galvanically isolated

Input range ……………………………………………………….. 12/24 Vdc (8 to 40 Vdc)

Input resistance………………………………………………………… approx. 20 kOhms

Relay outputs …………………………………..galvanically isolated / potential free

Contact material ……………………………………………………………………….. AgCdO

Load (GP) ……………………………………………………………… 2.00 Aac@250 Vac

2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc

Pilot duty (PD) ……………………………………………………………………………………..

1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc

Analog inputs (not isolated) …………………………………………..freely scalable

Type …………………………………………………………………… 0 to 10 V / 0 to 20 mA

Resolution …………………………………………………………………………………. 11 Bit

Housing  ……………………. Powder coated aluminum for back panel mounting

Dimensions WxHxD ………………… 250 × 227 × 84 mm (9.84 × 9.00 × 3.30 in)

Connection ………………………………………………. screw/plug terminals 2.5 mm²

Protection system ……………………………………………………………………….. IP 20

Weight ……………………………………………………………. approx. 1.900 g (4.2 lbs)

Disturbance test (CE) ………… tested according to applicable EN guidelines

Listings ………………………………………………………….. UL, cUL, GOST-R, CSA

Marine ………………………………….. LR (Type Approval), ABS (Type Approval)

Woodward MSLC-2™ Master Synchronizer and Load Control TYPICAL CONFIGURATION

 Applications for up to

32 generators with

16 mains and/or tie

breakers

 Configurable for mains

and tie breaker

applications

 Complex applications

with up to 8 bus

segments

 Automatic segment

recognition

 Redundant Ethernet

communication for

enhanced reliability

 The “system update”

feature allows for

system reconfiguration

 PLC and DCS compati

ble via Modbus RTU or

Modbus TCP

 Automatic plant loading

and unloading for bump

less load transfer to and

from the utility

 Controls plant wide

import/export levels

against the utility

 Overall plant Power

Factor control

 Ethernet or RS-232 port

for configuration of

device using Woodward

ToolKit software

 UL/cUL & CE Listed

Woodward MSLC-2™ Master Synchronizer and Load Control Applications

 The MSLC-2 hardware is adjustable for multiple applications.

 Slip frequency or voltage phase matching synchronizing fully selectable with dead bus option in both

directions provide full flexibility for intertie and main-tie-main applications.

 Having functions integrated into one box eliminates the need for redundant sensors (like PTs, CTs, and

MOPs) that connect to individual modules such as the load sensor and synchronizer.

 Digital signal processing makes the MSLC-2 resistant to power line distortions and harmonics.

 Three-phase true RMS power sensing provides accurate readings even with unbalanced phase loading

and voltage fluctuations.

 Export/import control over multiple utility MSLC-2’s in same segment.

 The Woodward ToolKit™ software allows flexible setup using the same basic menu tree as the original

MSLC plus an overview screen. No hand held programmer is required. Graphical overview of generators

and bus bar parameters with trending makes the MSLC-2 commissioning friendly.

 The Toolkit can be accessed either via one of the Ethernet ports or via RS-232 port.

 Phase angle compensation provides adjustment for additional deviation correction across a

transformer.

 The system update feature allows for system reconfiguration.

Woodward MSLC-2™ Master Synchronizer and Load Control FEATURES

FEATURES

 One MSLC-2 can provide master control for up to 32 DSLC and an additional 15 MSLC-2 in a system.

 Two dedicated Ethernet lines for precise system communications between all DSLC-2’s and

MSLC-2’s on the system.

 Ethernet Modbus TCP for remote control and monitoring by PLC or DCS system.

 Redundant Ethernet communications for enhanced reliability.

 Master MSLC-2 redundancy, loss of communications with the designated MSLC-2 master initiates

control hand off to the next designated MSLC-2 master.

 The MSLC-2 hardware is adjustable for multiple applications.

 Slip frequency or voltage phase matching synchronizing fully selectable with dead bus option in both

directions provide full flexibility for intertie and main-tie-main applications.

 Having functions integrated into one box eliminates the need for redundant sensors (like PTs, CTs, and

MOPs) that connect to individual modules such as the load sensor and synchronizer.

 Digital signal processing makes the MSLC-2 resistant to power line distortions and harmonics.

 Three-phase true RMS power sensing provides accurate readings even with unbalanced phase loading

and voltage fluctuations.

Woodward MSLC-2™ Master Synchronizer and Load Control

The MSLC-2 provides phase matching or slip frequency synchronization, with voltage matching,

across a utility or intertie breaker. The MSLC-2/DSLC-2 combination can handle multiple utility con

nections with a maximum of 8 bus segments in one application.

The MSLC-2’s load sensor and load control sense true RMS power and provide a bump-less load

ing and unloading against a utility grid. Baseload, import/export, process, and utility unload modes

control the KW power between different power sources at the same time controlling the reactive

power, VAR and power factor.  Reactive power is also ramped on and off for the smoothest load

transactions between power grids.

The MSLC-2 communicates via Ethernet, with redundant Ethernet now available, to control real

and reactive loading against the utility by DSLC-2 equipped generators.

The tie breaker mode allows synchronization between multiple generator systems. Segments are

connected and power can be measured across an intertie, but no load control is functional when in

Tie breaker operation.

Woodward MSLC-2™ Master Synchronizer and Load Control DESCRIPTION

DESCRIPTION

Woodward’s MSLC-2™ functions with the DSLC-2™ control to provide synchronization and load

control across Utility and Intertie breakers. The MSLC-2/DSLC-2 combination operates over an

Ethernet communication network to control simple or complex generator system applications. This

combination, 32 DSLC-2’s and 16 MSLC-2’s,  provide multiple unit, multiple segment, utility and

intertie power management for complex power systems. Controls plant wide Import / Export levels

while always providing bump-less load transfers with utility.

The MSLC-2 control combines synchronization, dead bus closing, utility/intertie load sensor, base

load control, import/export control, VAR, power factor, and a master process control in one power

ful package.

The MSLC-2 provides phase matching or slip frequency synchronization, with voltage matching,

across a utility or intertie breaker. The MSLC-2/DSLC-2 combination can handle multiple utility con

nections with a maximum of 8 bus segments in one application.