Welcome to the official website of CNIACS Automation Technology Co., Ltd!

Woodward easYgen-3400XT/3500XT Genset Control for Complex Paralleling Operation RELATED PRODUCTS

RELATED PRODUCTS

• Group Breaker Controller easYgen | GC-3000XT (Product Specification #37896)

• Excitation module for synchronous generators easYgen | exciter-10 (Product Specification #37909)

• Circuit Breaker Controller easYgen | LS-6XT, LS-511/521 & LS-512/LS-522 (Product Specification #37913. #37522 and #37661/37663)

• Remote Panel RP-3000XT (Product Specification # 37592)

• ToolKit (Product Specification # 03366)

• I/O Expansion Board IKD1 (Product Specification # 37171): P/N 8440-2116

• Engine Speed Control actiVgen (Product Specification # 03419): P/N 8440-2100

• Load Share Gateway LSG (Product Specification # 37451)

• Electronic Pickup Unit EPU-100 (Product Specification # 37562)

• CANbus based Remote Annunciator (Product Specification # 37279): easYlite 100 P/N 8446-1023

• Power Generation Learning Module (Product Specification # 03412): P/N 8447-1012

• Data TelegramMapper software (Application Note # 37684)

• Profibus Gateway (Application Note # 37577): ESEPRO P/N 8445-1046

• Remote Access Gateway (with HMS Netbiter EasyConnect EC250 and EC350)

• Modbus master software (Application Note # B37919)

• HMI localization tool (Product Specification # B37918)

• Thermocouple Scanner (AXIOMATIC AXTC20)

• WAGO and Phoenix expansion CAN Couple

Woodward easYgen-3400XT/3500XT Genset Control for Complex Paralleling Operation SPECIFICATIONS

SPECIFICATIONS

Power supply ………………………………………………….12/24 VDC (8 to 40 VDC)

Intrinsic consumption ……………………………….  max. 22 W (LT: max.32 W)

Ambient temperature (operation) …………… -20 to 70 °C (LT: -40 to 70 °C)

Ambient temperature (storage) …………………. -30 to 80 °C / -22 to 176 °F

Ambient humidity…………………………………………….. 95%, non-condensing

Voltage (software configurable) …………………………………………….. ( /)

100 VAC  Rated (Vrated) …………………………………….. 69/120 VAC

Max. value (Vmax) …………………………………….. 86/150 VAC

and 400 /600 VAC  Rated (Vrated)* …………………………………… 400/690 VAC

Max. value (Vmax) …………………………………… 520/897 VAC

Rated surge volt. (Vsurge) ……………………………………………. 6.0 kV

Accuracy …………………………………………………………………………. Class 0.5

Measurable alternator windings . 3p-3w, 3p-4w, 3p-4w OD, 1p-2w, 1p-3w

Setting range ………………. primary …………………………… 50 to 650.000 VAC

Linear measuring range …………………………………………………… 1.25×Vrated

Measuring frequency …………………………………….. 50/60 Hz (30 to 85 Hz)

High Impedance Input; Resistance per path …………………………… 2.5 M

Max. power consumption per path ………………………………………. < 0.15 W

Current (Isolated, software configurable)     Rated (Irated) ……… 1A or 5A

Linear measuring range ……………………………………………… Igen = 3.0×Irated

Imains/ground = 1.5×Irated

Setting range ……………………………………………………………… 1 to 32.000 A

Burden ……………………………………………………………………………. < 0.10 VA

Rated short-time overcurrent (1 s) ……………………[1] 50×Irated, [5] 10×Irated

Accuracy ………………………………………………………………………… Class 0.5

Power ……………………………………………………………………………………………

Setting range ……………………………………………….. 0.5 to 99.999.9 kW/kvar

Accuracy …………………………………………………………………………. Class 1.0

Discrete inputs …………………………………………………………………… isolated

Input range ……………………………………………………12/24 VDC (8 to 40 VDC)

Input resistance …………………………………………………… approx. 20 kOhms

Transistor outputs (P2 only) ………………………………………………… isolated

Rated switching voltage ………………………………………………… max. 24 VDC

Maximum switching voltage …………………………………………………… 40 VDC

Maximum switching current ……………………………………………. 300 mA DC

Isolation Test voltage (<1s) ………………………………………………….. 500 VAC

Isolation voltage (continuously) …………………………………………. 100 VAC/DC

Relay outputs ……………………………………………………………………… isolated

Contact material ………………………………………………………………….. AgCdO

Load (GP) …………………………………………………………… 2.00 AAC@250 VAC

2.00 ADC@24 VDC / 0.36 ADC@125 VDC / 0.18 ADC@250 VDC

Analog inputs (isolated) …………………………………………………freely scalable

Type 1 ………………………………………. 0 to 1 V / 0 to 2000 Ohms / 0 to 20 mA

Resolution ………………………………………………………………………………. 16 Bit

Maximum permissible voltage against genset Ground ……………………… 9 V

Maximum permissible voltage between genset Ground & PE ……….. 100 V

Type 2 (P2 only)…………………………………………………. 0 to 10 V / 0 to 20 mA

Resolution …………………………………………………………………………….. 14 Bit

Maximum permissible voltage against PE (Ground) …………………… 100 V

Maximum differential voltage to other DC Analog Inputs ………………. 15 V

Type 3 (P2 only)…………………………………. 0 to 250 Ohms / 0 to 2500 Ohms

Resolution …………………………………………………………………………….. 14 Bit

Maximum permissible voltage against PE (Ground) …………………… 100 V

Maximum differential voltage to other DC Analog Inputs ………………. 10 V

Analog outputs (isolated) ………………………………………………freely scalable

Type 1 ………………………………………………………….. ± 10 V / ± 20 mA / PWM

Basic insulation voltage (continuously, AVRout) ……………………….. 500 VAC

Reinforced insulation voltage (continuously, AVRout) ……………….. 300 VAC

Insulation voltage (continuously, Govout) ………………………………… 100 VAC

Resolution …………………………………………………………………………….. 12 Bit

Output ± 10 V (scalable) ……………………………………….. internal resistance

Output ± 20 mA (scalable) ………………………….. maximum load 500 Ohms

Type 2 (P2 only)……………………………………………………………… 0/4 to 20 mA

Insulation voltage (continuously) …………………………………………… 100 VAC

Insulation voltage (test; >2 s) ………………………………………………. 1700 VAC

Resolution …………………………………………………………………………….. 12 Bit

Output ……………………………………………………… maximum load 500 Ohms

Housing Front panel flush mounting ……………………………….. Plastic housing

Dimensions  WxHxD …………………………………… 282 × 216 × 96 mm

Front cutout  WxH ……………………………. 249 [+1.1] × 183 [+1.0] mm

Connection …………………………………………….. screw/plug terminals 2.5 mm²

Front ………………………………………………………………………. insulating surface

Sealing  Front ……………………………. IP66 (with screw fastening)

Front ……………………………. IP54 (with clamp fastening)

Back ……………………………………………………………. IP20

Weight ………………………………………………………………………. approx. 1.850 g

Housing Back panel mounting …………. Powder Coated Sheet metal housing

Dimensions  WxHxD  P1: …………………………….. 250 × 228 × 50 mm

P2: …………………………….. 250 × 228 × 84 mm

Connection …………………………………………….. screw/plug terminals 2.5 mm²

Protection system ……………………………………………………………………… IP 20

Weight ………………………………………………………………………. approx. 1.750 g

Disturbance test (CE) ………… tested according to applicable IEC standards

Listings  ……………………………… CE, UL, EAC, VDE-AR-N 4105/ 4110. CSA

Marine ………………………………….. LR (Type Approval), ABS (Type Approval)

Woodward easYgen-3400XT/3500XT Genset Control for Complex Paralleling Operation FEATURES Cylinder head

• Freely configurable PID controllers for various control purposes, such as heating circuit control (CHP applications), water level, fuel level, pres

sure and / or other process variables

• Direct support to several ECUs: Scania S6. MTU ADEC ECU7/8/9. Volvo EMS2 & EDC4. Deutz EMR2 & EMR3. MAN MFR / EDC7. SISU

EEM, Cummins and Woodward EGS02 ECU

• Modbus master and modbus data telegram mapper support with dedicated PC tools

• CAN J1939 support to exhaust gas after-treatment (DPF, SCR) triggered by global diesel emissions regulations

• „System Update“ function ensures every unit recognizes other units in the network and helps isolate root-cause quickly during troubleshooting

• Time / Date synchronization over Simple Network Time Protocol (SNTP)

• Cylinder head / exhaust temperature monitoring (Temperatures come from J1939 or CANopen devices)

• Woodward ToolKit™ software for flexible setup from a single connection to the network. The ToolKit can be accessed either via USB, or via

Ethernet, or via CAN ports.

• Multi-lingual capability: English, German, Spanish, French, Italian, Portuguese, Japanese, Chinese, Russian, Turkish, Polish, Slovakian, Finn

ish, Swedish and an empty slot for custom language via a dedicated MS Excel based PC tool

Woodward easYgen-3400XT/3500XT Genset Control for Complex Paralleling Operation FEATURES Load transfer

• Run-up synchronization / Dead Field Paralleling to quickly get several synchronous generators onto the load

• Three-phase true RMS power sensing with Class I accuracy

• Operation modes: AUTO, STOP, MANUAL, and TEST – accessible through face plate or discrete input

• Breaker control: Slip frequency / phase matching synchronization, open / close control, breaker monitoring

• Load transfer: open / closed transition, interchange, soft loading / unloading, Utility parallel

• Load share and device to device communication over CAN, Ethernet or hot redundant ETH/ETH, CAN/ETH

• Remote control via interface (Modbus TCP, Modbus RTU) and via discrete/analog inputs for adjusting

speed, frequency, voltage, power, reactive power, and power factor set points

• Freely configurable PID controllers for various control purposes, such as heating circuit control (CHP applications), water level, fuel level, pres

sure and / or other process variables

• Direct support to several ECUs: Scania S6. MTU ADEC ECU7/8/9. Volvo EMS2 & EDC4. Deutz EMR2 & EMR3. MAN MFR / EDC7. SISU

EEM, Cummins and Woodward EGS02 ECU

Woodward easYgen-3400XT/3500XT Genset Control for Complex Paralleling Operation FEATURES

FEATURES

• Enables several power generation topologies. Some frequently used are:

• only with easYgen-3500XT: 32 gensets, one generator group breaker and one mains circuit breaker

• with easYgen-3500XT and LS-5: 32 gensets and 16 breakers (Tie/GGB/MCB) or 16 gensets and 32

breakers on CAN bus

• with easYgen-3500XT and LS-6XT:  32 gensets and 32 breakers (Tie/GGB/MCB) on single or redundant

Modbus/TCP

• with easYgen-3500XT and GC-3000XT: 496 gensets, one generator group breaker and one mains circuit breaker

• with easYgen-3500XT, LS-6XT and GC-3000XT: The control topology is cascaded in three layers. Layer

1 consists of easYgen (and also LS-6XT), Layer-2 group controls and Layer-3 LS-6XT. At Layer-1 total

496 gensets (16 x 31), at Layer-2 16 Group controllers and at Layer-3 64 LS-6XT on up to 128 segments

are supported. Communication between Layer-1 and Layer-2 controls is CAN, Ethernet A or hot redun

dant CAN/Ethernet A and between Layer-2 and Layer-3 controls is Ethernet B, Ethernet C or hot redun dant Eth B/Eth C.

Woodward easYgen-3400XT/3500XT Genset Control for Complex Paralleling Operation DESCRIPTION engine-generator

The control combines complete engine-generator con

trol and protection with advanced, peer-to-peer paralleling functionality and innovative features in a robust, at

tractive, user-friendly and all-in-one package. The easYgen-3500 XT controls are designed to direct connect up

to 690Vac and operate to 4000m above sea level without derating.

The easYgen-3500XT is available in two packages. P1. focused at complex paralleling applications provides

redundant Ethernet communication, LS-5 connectivity, and standard I/O set, while P2. Co-Gen/CHP model

offers expanded onboard I/O set, 3-ph busbar voltage measurement capability and phase rotation monitoring

between gen-busbar and busbar-utility. These packages are available without a display in a rugged metal hous

ing suitable for back panel installations (easYgen-3400XT-P1 and easYgen-3400XT-P2 respectively). A sophis

ticated touch screen remote panel (RP-3000XT) complements them as an operator control panel.

A version of easYgen-3500XT (easYgen-3500XT-P1-LT and easYgen-3500XT-P2-LT) is designed to operate

down to -400 C for outdoor applications.

Woodward easYgen-3400XT/3500XT Genset Control for Complex Paralleling Operation DESCRIPTION

DESCRIPTION

Woodward raised the standard in genset paralleling control and power management system with the easYgen

3000XT Series controllers. These controllers come with standardized software that is simple to configure, yet

easily customized for individual applications. Enhanced connectivity enables fast, reliable and secure interfac

ing to other controls and communications systems while the enhanced hardware is a drop-in replacement for

previous generation easYgen-3000 Series Controls.

Targeted at enabling complex power management applications, the easYgen-3500XT supports easYgen | GC

3000XT to manage a large genset fleet of up to 496 sets and easYgen | LS-6XT to control up to 64 synchroniz

ing breaker or manual switches on up to 128 complex bus segments. Redundant load sharing is selectable us

ing Ethernet B and C networks for enhanced reliability. The control combines complete engine-generator con

trol and protection with advanced, peer-to-peer paralleling functionality and innovative features in a robust, at

tractive, user-friendly and all-in-one package. The easYgen-3500 XT controls are designed to direct connect up

to 690Vac and operate to 4000m above sea level without derating.

Woodward easYgen-3400XT/3500XT Genset Control for Complex Paralleling Operation

New Features

✓ Built-In Redundant Ethernet

✓ Power Measurement Class 1

✓ Direct Connect Up to 690 VAC

✓ AnalogManager & Editable Screens

✓ Multi-Interface ToolKit connectivity

✓ Face plate with tactile buttons

✓ Drop-In replacement

• Premium genset control for complex paralleling applications of up to 32 gensets in

• Prime Power & Cogeneration (CHP)

• Peak shaving operation

• Emergency operation

• Import/Export operation

• Islanded & Utility parallel operation

• Group controller and LS 6XT support to manage large fleet of gensets and circuit breakers

• Run-Up Synchronization

• Built-in active voltage regulation

• Complete engine, generator and utility protection

• Up to 9 communication ports: 3xEthernet, 3xCAN (CANOpen and J1939), RS-485. USB, Interface expansion card

• Customizable logic, HMI screens, and alarms

• Dedicated low temperature display variants

• UL 61010. UL 6200. CSA, RoHS 2. and marine (ABS, LR) compliance

Woodward easYgen-3100XT/3200XT Genset Control for Multiple Unit Operation

New Features

✓ Redundant CAN/Ethernet connectivity

✓ AnalogManager

✓ Power Measurement Class 1

✓ Editable Screens

✓ Multiple interface ToolKit connectivity

✓ Face plate with tactile buttons

✓ Drop-In replacement

• Standard paralleling applications for up to 32 generators in

• Peak shaving operation

• Stand-by operation

• AMF (Automatic Mains Failure) operation

• Emergency operation

• Import/Export operation

• Islanded & Utility parallel operation

• Easy to set up and commission

• Master or Slave control capability

• Complete engine, generator and utility protection

• Open/Closed Transition

• Five communication ports: Ethernet, 2xCAN (CANOpen and J1939), RS-485. USB

• Customizable logic, HMI screens, and alarms

• Dedicated low temperature display variants

• UL 61010. UL 6200. CSA, RoHS 2. and marine (ABS, LR) compliance

Woodward easYgen-3100/3200 Genset Control for Multiple Unit Operation SPECIFICATIONS

SPECIFICATIONS

Power supply …………………………………………………. 12/24 Vdc (8 to 40 Vdc)

Intrinsic consumption ………………………………………………………… max. 17 W

Ambient temperature (operation) ………………….. -20 to 70 °C / -4 to 158 °F

Ambient temperature (storage) …………………… -30 to 80 °C / -22 to 176 °F

Ambient humidity……………………………………………… 95 %, non-condensing

Voltage ………………………………………………………………………………….. ( /∆)

100 Vac [1] Rated (Vrated) …………………………………….. 69/120 Vac

Max. value (Vmax) …………………………………….. 86/150 Vac

Rated surge volt.(Vsurge) ……………………………………………. 2.5 kV

and 400 Vac [4] Rated (Vrated) …………………………………… 277/480 Vac

Max. value (Vmax) …………………………………… 346/600 Vac

Rated surge volt.(Vsurge) ……………………………………………. 4.0 kV

Accuracy ……………………………………………………………………………… Class 1

Measurable alternator windings … 3p-3w, 3p-4w, 3p-4w OD, 1p-2w, 1p-3w

Setting range ………………… primary ……………………………50 to 650.000 Vac

Linear measuring range …………………………………………………….. 1.25×Vrated

Measuring frequency……………………………………….. 50/60 Hz (40 to 85 Hz)

High Impedance Input; Resistance per path ……. [1] 0.498 MΩ, [4] 2.0 MΩ

Max. power consumption per path ………………………………………… < 0.15 W

Current (Isolated) Rated (Irated) ………………………… [1] ../1 A or [5] ../5 A

Linear measuring range ……………………………………………….. Igen = 3.0×Irated

Imains/ground = 1.5×Irated

Setting range ……………………………………………………………….. 1 to 32.000 A

Burden ……………………………………………………………………………… < 0.15 VA

Rated short-time current (1 s) ……………………………[1] 50×Irated, [5] 10×Irated

Power ……………………………………………………………………………………………

Setting range …………………………………………………. 0.5 to 99.999.9 kW/kvar

Discrete inputs …………………………………………………………………… isolated

Input range ……………………………………………………. 12/24 Vdc (8 to 40 Vdc)

Input resistance …………………………………………………….. approx. 20 kOhms

Relay outputs ………………………………………………………………………… isolated

Contact material ……………………………………………………………………….. AgCdO

Load (GP) ……………………………………………………………… 2.00 Aac@250 Vac

2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc

Pilot duty (PD) ……………………………………………………………………………………..

1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc

Analog inputs (none isolated) ………………………………………freely scaleable

Type ………………………………………………………….. 0 to 500 Ohms / 0 to 20 mA

Resolution …………………………………………………………………………………. 11 Bit

Analog outputs (isolated) …………………………………………….freely scaleable

Type ………………………………………………………………. ± 10 V / ± 20 mA / PWM

Insulation voltage (continuously) ………………………………………………. 100 Vac

Insulation test voltage (1s) ……………………………………………………….. 500 Vac

Resolution ………………………………….. 11/12 Bit (depending on analog output)

± 10 V (scaleable) ……………………………………. internal resistance ≤1 kOhms

± 20 mA (scaleable) ………………………………………. maximum load 500 Ohms

Housing  Front panel flush mounting ……………… Plastic housing

Dimensions  WxHxD …………………………………… 282 × 217 × 99 mm

Front cutout  WxH ……………………………. 249 [+1.1] × 183 [+1.0] mm

Connection ………………………………………………. screw/plug terminals 2.5 mm²

Front ………………………………………………………………………… insulating surface

Sealing  Front ……………………………. IP66 (with screw fastening)

Front ……………………………. IP54 (with clamp fastening)

Back ……………………………………………………………. IP20

Weight ………………………………………………………………………… approx. 1.850 g

Housing  Switch cabinet back mounting ….. Sheet metal housing

Dimensions  WxHxD …………………………………… 250 × 227 × 84 mm

Connection ………………………………………………. screw/plug terminals 2.5 mm²

Protection system ……………………………………………………………………….. IP 20

Weight ………………………………………………………………………… approx. 2.150 g

Disturbance test (CE) ………… tested according to applicable EN guidelines

Listings ………………………………………………………….. UL, cUL, GOST-R, CSA

Marine …………………………… LR (Type Approval), ABS (Design Assessment)