Welcome to the official website of CNIACS Automation Technology Co., Ltd!

ABB Binary Input Board 23BE50 for isolated input of 64 groups of 4 process signals

APPLICATIONS

The Binary Input Board 23BE50 is used for the isolated input of 64 process signals divided into 4 groups of up to 16 binary signals each.

The input signals are scanned and processed with a time resolution of up to 1 ms.

The input signals can be assigned to processing functions according to configurable rules. The board 23BE50 can process the following types of signals:

 64 time-stamped single indications

 32 time-stamped dual indications

 8-step position information www.cniacs.com with 8 bits per step

 8/16-bit digital measurements

 8/16-bit string information

 64 pulse counters (max. 120 Hz)

These modules require the 560PSU40/41 power supply.

Features

All inputs are potentially isolated via optocouplers. If a common loop is required, this can be realized with external shorting connectors, which are included in the delivery.

Typical input current on the inputs is 1.5 mA.

There are 64 LEDs on the board to indicate the signal status. The LEDs are divided into two columns and follow the inputs directly.

The binary input board 23BE50 performs the following processing functions for different types of signals:

 Digital filtering to suppress contact jumping

 Suppression of technically induced chattering signals

 Intermediate position suppression and double indication monitoring

 Consistency check of all binary input channels assigned to digital measurement values

ABB 23BE23 Datasheet Binary Inputs 16-Channel LEDs

Applications

The binary input module 23BE23 provides 16 current-isolated

inputs for up to 16 binary process signals. Scanning and pro

stopping of the inputs is performed with a high time resolution of

of 1 millisecond. The assignment of input signals to process functions

can be adjusted according to the configuration rules.

Module 23BE23 is capable of processing the following types of

signals or combinations of them.

– 16 single point messages with time stamp (SPI)

8 double-point messages with time stamp (DPI)

– 2 digital measurements of 8 bits each (DMI8)

One 16-bit digital measurement (DM16)

– 16 integrated totals (max. 120 Hz) (ITI)

– 2 step position information, 8 bits each (STI)

2 bit string inputs, 8 bits each (BSI8)

One 16-bit bit string input (BSI16)

One or a combination of these signal types

The module allows process voltages from 24 to 60 VDC. Light Emitting Diode

Signals are provided for all inputs. The module has a common return of every 8 inputs.

Characteristics

Binary Inputs

The inputs are electrically isolated by means of optocouplers.

The 8 inputs are constructed as a group with a common return. Inputs

The circuitry is designed to keep the input current constant with a current regulator 1 = pole.

The module has 16 LEDs ,which are www.cniacs.com used to indicate the signal status of the inputs.

The LEDs directly follow the input signal.

The maximum permissible frequency of the inverse pulse is 120 Hz.

ABB 560BIR01 Binary Input Module 8 Channels LEDs

Binary input module with 16 channels for single indication, dual indication, digital gauges and pulse counters

– Resolution 1ms

– Process voltage: 24…. 24…60 V DC / 110…125 V DC . 125 V DC

– LED signal per input

– Common return signal per 8 inputs

APPLICATIONS

The module 560BIR01 provides 16 galvanically isolated inputs for up to 16 binary process signals.

The input signals are scanned and processed with a time resolution of up to 1 ms. The input signals can be assigned to processing functions according to configuration rules.

The module 560BIR01 can process the following types of signals or combinations of signals:

– 16 time-stamped single-point messages (SPI)

– 8 time-stamped double-point messages (DPI)

– 2 8-bit digital measurements (DMI8)

– 1 16-bit digital measurement (DMI16)

– 16 integrated totals (max. 120 Hz) (ITI)

– 2 step position information, 8 bits each (STI)

– 2 bit string inputs, 8 bits each (BSI8)

– 1 16-bit bit string input (BSI16)

– or a combination of these signal types

The module is available in two versions (rubrics):

– 560BIR01 R0001: Process voltage www.cniacs.com 24 to 60 V DC.

Each input is signalized with an LED and every 8 inputs have a common loop.

– 560BIR01 R0002: Process voltage 110 to 125 V DC.

Each input is signaled by an LED and each of the 8 inputs has a common loop.

Characteristics

Binary inputs

The inputs are galvanically isolated by means of an optocoupler. 8 inputs are grouped together and have a common return.

The input circuitry maintains a constant input current through the use of a current regulator diode.

The binary input channels are reverse voltage protected. If the input signal is of the wrong polarity, the input current will be zero.

The module has 16 LEDs to indicate the signal status of the inputs. the LEDs directly indicate the input signals.

The maximum permissible frequency of the counter pulses is 120 Hz.

ABB Secure and Analyze MobileGuard™ Natural Gas Leak Detection System

Traditional leak detection processes do not meet today’s demands for fast, accurate and transparent data. The storage and transportation of flammable or hazardous gases poses safety and environmental risks.

The natural gas industry and utilities are facing increasing challenges in pipeline monitoring and compliance for the following reasons

– Aging infrastructure

– Regulatory pressure to improve system integrity

– Desire to reduce greenhouse gas emissions

– Reliance on time-consuming, error-prone paper-based monitoring systems

– Pressure to reduce costs

– Need for data transparency

Current leak detection methods are slow, costly and often unreliable, ABB’s solutions can quickly detect, find and quantify leaks anywhere.

ABB’s natural gas leak detection systems directly address all these challenges:

– Local gas distribution systems

– Surveying mains and services

– Odor surveys

– Construction verification

– Post-disaster assessments

– Frost Line Assessment

Benefits

– Reliable – Measures methane and ethane simultaneously, eliminating false alarms

– Time saving – leaks can be detected within 2 minutes of energization (comparable laser methods require 30 to 45 minutes to warm up and/or are much less sensitive)

– Less maintenance – unlike other laser methods, ABB’s patented technology is robust and can be fully serviced by anyone, anywhere, anytime

– Lower operating costs

– Cybersecurity – ABB solutions are fully tested to www.cniacs.com meet stringent cybersecurity requirements

– Data integrity – the customer owns and controls the instrument at all times and has full custody of all data

– Transparency – data is available anytime, anywhere through cloud-based reporting

ABB launches Sensi+™ – a revolutionary analyzer for natural gas quality monitoring

– Single unit for continuous, simultaneous measurement of contaminants in H2 small, high 2O and CO2 natural gas streams for trade handover, tariff compliance and process monitoring

– ABB’s proven laser technology virtually eliminates false readings and provides fast response for reliable process control

– Designed for remote and hazardous locations, Sensi+ delivers superior performance and low cost of ownership

ABB’s Sensi+ analyzer offers a reliable new solution that www.cniacs.com simplifies and reduces pipeline operation and maintenance costs.

It enables safer, easier and more efficient pipeline monitoring and operation with a single device that

The device can analyze up to three contaminants (H2 minor, 2O major, CO2) accurately and in real time in any natural gas stream.

Its fast response also enables quick reaction to process disturbances, which can help reduce waste and methane emissions.

Reducing the risk and impact of natural gas contaminants often presents challenges for natural gas pipeline operators, the processing industry and natural gas utilities.

ABB Ability™ SmartMaster

About ABB Ability™ SmartMaster

ABB Ability SmartMaster is a next generation

ABB Ability SmartMaster is the next generation suite of validation tools and condition monitoring platforms for use with a range of ABB equipment. By downloading the software, including the associated Validation Definition File (VDF), you can

Optimize the checking of measurement accuracy without stopping the process. Using a licensed version of the software, test reports can be generated and stored locally for further analysis.

Based on ABB’s “fingerprint” concept, every unit is subjected to a verification test before leaving the factory. Based on ABB’s fingerprinting concept, every unit is subjected to a verification test before leaving the factory.

After the product has been commissioned, the operator has the option via software to use the factory fingerprints or to create new fingerprints based on actual site conditions.

SmartMaster is a solution that has been developed as a platform to remotely verify equipment diagnostic data without interrupting ongoing measurements:

– ABB DCS and FIM Connectivity

– Cell phone connectivity

– Bluetooth connectivity

– Ethernet (OPC UA) connection

SmartMaster Features

Advanced features

– Support for up to 400 assets

– Scheduled Validation

– Accuracy statement for test equipment

– Parameter level trending

– Service recommendations

– Data storage up to 5 years

Advanced

– Supports up to 150 www.cniacs.com assets

– Includes licensed software testing

– Accuracy statement for test equipment

– Report generation

– Historical validation data (viewed monthly)

– Instrument diagnostic information

– Cause and recommended action

ABB HMI560 560SFR02 Rack available with or without redundant power supply

Applications

The 560SFR02 rack can be used with or without redundant power supplies. Therefore, it has 2 slots for redundant power supply units (PSUs)

It therefore has 2 slots for redundant power supply units (PSUs) and 17 slots that can be used for I/O boards, communication units (CMUs), or a combination of both. It connects to other racks via the RTU560s serial peripheral bus.

Up to seven 560SFR02 racks can be connected to one system.

By using the Bus Connection Unit 560BCU05. up to 8 Communication Units (560CMU05/560CMU02R2) can be connected to the 560SFR02.

For applications with only one communication unit, the BCU05 is also required.

The BCU05 can be installed in a swing-out cabinet or frame.

A second PSU can only be inserted and made operational in slot 19. Insertion of other modules is not allowed.

If the second PSU option is not used, slot 18 can be used.

Features

19” rack height of 3 HE for single Eurocard format boards (DIN 41494). A total of 20 slots are available for mounting boards.

Each PSU has one predefined slot (slot 21 and slot 19). These slots can only be used with PSU modules.

Slots 1 through 17 can be used for I/O boards and/or www.cniacs.com CMU modules. If redundant power supplies are not used, slot 18 can be used to install additional I/O boards.

Slot assignment:

Two slots for

x 1 or 2 power supply units (each 2 slots wide)

17 slots for

x up to 8 communication units

x up to 17 I/O boards (with redundant power supply)

x up to 18 I/O boards (if only one power supply unit is used)

ABB 23BA23 Board Command Output Monitor Module Board

APPLICATIONS

The 23BA23 board is used for the remote terminal unit RTU560.

The 23BA23 board should be installed if you need to check the output circuitry for object commands before issuing the actual command.

The 23BA23 board performs an “n select 1” check. It checks whether only one intermediate relay is activated in the output circuit.

This is only feasible if all mutually exclusive relays connected to a check circuit have the same resistance value. have the same resistance value.

23BA23 The board allows two separate check circuits to be used to check two different types of interlocking relays.

The allowable tolerance ranges are defined by parameters.

A maximum of 16 23BA23 boards can be used with one RTU560.

In RTU560 systems, the 23BA23 board is only functionally and pinout compatible with the 23BA22 board.

The 23BA23 board is only functionally and pin compatible www.cniacs.com with the 23BA22 board in an RTU560 system.

The basic additional tasks are as follows

Checking the galvanic isolation of the circuit

Suppress line frequency during measurement

Characteristics

Figure 1 shows the connection of the binary output boards 23BA20 and 23BA23 at two-pole startup for (n select 1) checking.

The check circuit for measuring the relay coil resistance is galvanically isolated from the electronic voltage and the switching voltage (UD) of the intermediate relay.

This is achieved by means of galvanically isolated DC/DC converters and optocouplers.

No auxiliary test voltage is required. During the measurement, the 23BA23 board switches the corresponding check circuit (P1 or P2) to both poles, thus separating the two.

During the check (1 out of n), the 23BA23 board measures the resistance value in the output circuit and compares this value with the configured upper and lower limits.

If the resistance value is within the limit values, the selected interlock relay can be activated. The object command will be acknowledged.

If the measured resistance value is outside the permissible range, the 23BA23 blocks the output and displays an error to the CMU (CMU = communication unit).

The CMU controls and coordinates the corresponding 23BA20 and 23BA23 boards.

ABB 23OK24 Fibre optic coupler Serial communications

Fiber optic coupler for glass fiber optic cables with an emission wavelength of 820 nm Fiber optic connection with bayonet socket BFOC/2.5 (IEC-SC86B)

Optical isolation of the RTU560 bus

Suitable for use as star coupler for RS-485 and RS-232 buses

IEC 60870-5-103 device interface

Front panel connector for 2 optical lines

Fiber optic coupler 23OK24

The fiber optic coupler 23OK24 is suitable for the RTU560. the module is used to transmit data via 2 independent optical links (receive and transmit).

Fiber optic cables are insensitive to inductive and capacitive interference as well as to potential differences between the two data communication devices.

In critical environments or when potential isolation is required, fiber optic cables can be used to bridge across distances. With 200 μm fiber optic cables, the maximum distance is up to 2600 meters.

The module can be used to convert the receive and transmit data signals of the following electrical interface standards to fiber optic signals:

– RTU560 SPB I/O bus

– RS-485 bus

– RS-232 C

The fiber optic coupler 23OK24 can be www.cniacs.com connected to the RTU500 series coupler 560FOC40. the RTU520 I/O adapter 520ADD03 R0002 and the RTU511 I/O adapter 23AD64 R0002.

ABB 23WT23 PCB Modem Serial Communications

APPLICATIONS

The 23WT23 board is a modem that converts serial data according to the CCITT V.23 standard.

Therefore, it can be used for transmission over leased PTT lines, private networks or radios.

The two-wire or four-wire mode of operation can be selected via jumpers. The Voice Frequency (VF) output has a high impedance and can connect up to 10 remote stations to multiple pull-down lines.

The modem 23WT23 is available in two versions (rubrics):

– R0001: 5 VDC power supply

– R0002: 24 VDC power supply

Features

The 23WT23 circuit board is a printed circuit in Eurocard (160 mm x 100 mm) format.

All necessary configurations, such as transmit-output level, receiver sensitivity, and two- or four-wire operation, can be configured via jumpers.

The interface to the Data Terminal Equipment (DTE) operates according to the RS 232-C standard and provides the following signals:

– TxD Transmit Data

– RxD Receive Data

– RTS request to send

– DCD Data carrier detect

– CTS Clear to transmit

– DSR Data setup ready

The receiver level is monitored and the alarm relay, together with the light-emitting diode (LED) “ST”, indicates a longer (approx. 4-6 seconds) interruption of the carrier.

The LED on the front panel shows the signal status of the RS 232-C interface. The serial interface signals as well as the VFT line can be measured or opened using the disconnect test socket on the front panel.

If a higher isolation voltage is required, an additional VF signal transformer must be used.

Optionally, surge voltage protection www.cniacs.com elements can be inserted on request to protect against transient overvoltage spikes (see Figure 2).

The 23WT23 modem operates according to the CCITT V.23 standard in half and full duplex mode at 1200 bits/second.

The R002 version is compatible with the 23WT21 modem connector and can only be used in the RTU232 base subrack. In all other cases, the 5-volt version of R0001 should be used.

Search for products

Back to Top
Product has been added to your cart