ABB The IEC 61850 standard specifies an expandable data model

The IEC 61850 standard specifies an expandable data model and services for

substation automation (standard parts 7-x). The standard does not specify any

protection or control functions, but specifies how the functions expose their

information to a communication network.

The standard supports free allocation of functions to devices. With efficient

communication facilities, the functions can be located anywhere in the system, that

is, an interlocking function can reside in the IED or on the station level.

Additionally, the standard is open for different system implementations, that is,

different integration levels and allocation of functions to different devices is

supported.The standard also defines an XML description language for substation automation

systems. The language facilitates efficient integration of devices into systems in an

automated fashion. Additionally the standard supports a comprehensive and

consistent system definition and engineering, which makes not only the devices,

but also their tools and systems interoperable (standard part 6).

ABB The international IEC 61850 standard defines a framework

The international IEC 61850 standard defines a framework for substation

communications networks and systems. The standard consists of several parts

ranging from the requirements on substation automation systems to the details of a

communication protocol.

One major difference between the other communication protocols applied in

substation automation and IEC 61850 is that the latter is not only a communication

protocol, but a whole framework for specifying, engineering and operating

substation automation systems. The communication part covers the connection

between the IEDs and the substation clients, for example, SCADA and gateways.

The standard also defines an XML description language for substation automation

systems. The language facilitates efficient integration of devices into systems in an

automated fashion. Additionally the standard supports a comprehensive and

consistent system definition and engineering, which makes not only the devices,

but also their tools and systems interoperable (standard part 6).

The standard uses Ethernet and TCP/IP for communication. Since Ethernet and TCP/

IP are widely accepted and used, the application of these technologies provide a

broad range of features from mainstream communication (standard parts 8-1. 9-2).

However, IEC 61850 is also open for possible new communication concepts in the

future.

ABB REF615 ANSI Communication

Communication

• IEC 61850-8-1 with GOOSE messaging

• DNP3.0 Level 2+ over TCP/IP

• Modbus over TCP/IP

• Time synchronization via SNTP (primary and backup servers)

• Optional serial RS-485 port programmable for

DNP3.0 Level 2+ or Modbus RTU

• Optional IRIG-B time synchronization

• Optional HSR/PRP communication

• Optional IEEE1588v2 time synchronization (available

with REF615 V5.0 and later)

• IEC61850-9-2LE (available with REF615 V5.0 and later)

Tools

• PCM600 V2.8 for setting, configuration and data retrieval

• COM600 Station Automation series products V5.0

• Web browser based user interface (IE 11 or later)

Certificates

• UL Listed product, File E103204

Control voltage

• Option 1: 48 … 250 V dc, 100 … 240 V ac

• Option 2: 24 … 60 V dc

ABB REF615 ANSI Binary inputs and outputs

Analog inputs

• Three phase currents: 5/1 A programmable

• Ground current: 5/1 A programmable or 0.2 A

Rated frequency: 60/50 Hz programmable

• Three-phase and ground voltages: programmable

nominal secondary voltage (available as options)

Binary inputs and outputs

• Four, eight with VT inputs, binary inputs standard

• Two NO outputs with trip circuit monitoring

• Three NO outputs

• One Form C output and self-check alarm output

• Additional binary inputs and outputs available as options

Product dimensions and weights

• Frame: 6.97” (177 mm) W x 6.97” (177 mm) H

• Case: 6.57” (165 mm) W x 6.30” (160 mm) H x 6.10”

(155 mm)

• Weight: Relay – 7.72 lbs. (3.5 kg); Draw-out unit – 3.97

lbs. (1.8 kg)

ABB REF615 supports the new IEC 61850 standard

Standardized communication

REF615 supports the new IEC 61850 standard for in

ter-device communication in substations. The relay

also supports the industry standard DNP3.0 and Mod

bus® protocols. The implementation of the IEC 61850

substation communication standard in REF615 en

compasses both vertical and horizontal communica

tion, including GOOSE messaging and parameter set

ting according to IEC 61850-8-1. The substation

configuration language enables the use of engi

neering tools for automated configuration, com

missioning, and maintenance of substation devices.

ABB REF615 ANSI Pre-emptive condition monitoring

Pre-emptive condition monitoring

For continuous knowledge of the operational avail

ability of the REF615 features, a comprehensive set

of monitoring functions to supervise the relay

health, the trip circuit, and the circuit breaker

health is included. The breaker monitoring can in

clude checking the wear and tear of the circuit

breaker, the spring charging time of the breaker

operating mechanism and the gas pressure of the

breaker chambers. The relay also monitors the

breaker travel time and the number of circuit

breaker operations to provide basic information

for scheduling breaker maintenance.

ABB The IEC 61850 implementation Bus protection via GOOSE

Bus protection via GOOSE

The IEC 61850 implementation in REF615 also in

cludes fast peer-to-peer communication, over the

substation bus. Use GOOSE communication be

tween REF615 IEDs of the incoming and outgoing

feeders of a substation cooperate to form a stable,

reliable, and high-speed busbar protection system.

The cost-effective GOOSE-based busbar protec

tion is obtained by configuring the IEDs and the

operational availability of the protection is assured

by continuous supervision of the protection IEDs

and their GOOSE messaging over the station bus.

No separate hard-wiring is needed for the horizon

tal communication between the switchgear cubicles.

ABB The REF615 is a dedicated feeder protection and control relay

The REF615 is a dedicated feeder protection and control relay perfectly

aligned for the protection, control,measurement and supervision of

utility substations and industrialpower systems.

REF615 is a member of ABB’s Relion® family and a part

of its 615 protection and control product series. The

615 series protection and control relays are character

ized by their compactness and withdrawable design.

Engineered from the ground up, the 615 series has

been designed to unleash the full potential of the IEC

61850 standard for communication and interoperabil

ity of substation automation devices.

Application

The REF615 provides main protection for overhead

lines, cable feeders, and busbar systems of distribu

tion substations. It can be applied for protection and

control of grounded and ungrounded distribution sys

tems. Flexible order coding allows for choosing cur

rent-only or current-and-voltage configurations to

best fit your distribution feeder application needs.

ABB REF615 ANSI Feeder Protection and control

Protection and control

The REF615 is the most powerful, advanced and sim

plest feeder protection relay in its class, perfectly of

fering time and instantaneous overcurrent, negative

sequence overcurrent, phase discontinuity, breaker

failure, thermal overload, and voltage metering and

protection. The relay also features optional high im

pedance fault (HIZ) protection for grounded and un

grounded distribution systems. Also, the relay incor

porates a flexible three-phase multi-shot auto-reclose

function for automatic feeder restoration in tempo

rary faults on overhead lines.

Enhanced with safety options, the relay offers a

three-channel arc-fault detection system for supervi

sion of the switchgear.

The REF615 also integrates basic control functionality,

which facilitates the control of one circuit breaker via

the relay’s front panel human machine interface (HMI)

or remote control system. To protect the relay from

unauthorized access and to maintain the integrity of

information, the relay has been provided with a four

level, role-based user authentication system, with in

dividual passwords for the viewer, operator, engineer,

and administrator levels. The access control system

applies to the front panel HMI, embedded web

browser based HMI, and the PCM600 relay setting and

configuration tool.

ABB REF615R Feeder protection and control

Analog inputs

− Three phase currents: 5/1 A programmable

− Ground current: 5/1 A programmable or 0.2 A

− Rated frequency: 60/50 Hz programmable

− Three-phase and ground voltages: programmable nominal

secondary voltage

Binary inputs and outputs

− Eleven binary inputs standard

− Seven programmable outputs

− Three outputs configurable to NO or NC standard. One con

figurable output if HSO option is selected.

− One Form C self-check alarm output

− High-speed outputs (HSO) optional

Communication

− IEC 61850-8-1 with GOOSE messaging

− DNP3.0 Level 2+ over TCP/IP

− Modbus over TCP/IP

− Time synchronization via SNTP (primary and backup servers)

− Optional serial RS-485 port programmable for DNP3.0 Level

2+ or Modbus RTU

− Optional IRIG-B time synchronization

Search for products

Back to Top
Product has been added to your cart