Welcome to the official website of CNIACS Automation Technology Co., Ltd!

ABB Real Time Clock 560RTC02 RTU560 Product Family

Real-Time Clock RTU560 Standard Time Synchronization with Longwave Transmitter DCF7

Applications

RTU560 product line units can be synchronized with the standard time of the longwave transmitter DCF77 using the module 560RTC02.

The RTU560 reads the time and date from the module 560RTC02 and synchronizes its internal clock with standard time via minute pulses.

The RTU560 synchronizes its internal clock with standard time by means of minute pulses. The use of the module 560RTC02 ensures that the indications of several end devices are synchronized when they contain time information.

Features

The longwave DCF 77 transmitter can be reliably www.cniacs.com received within a distance of approx. 1500 kilometers from Frankfurt/Main in West Germany, as well as in many parts of Europe.

If the reception level is sufficient, the module 560RTC02 will synchronize with standard time and receive the date and time within three minutes.

The communication unit (CMU) is synchronized with DCF 77 via the MIN1 pulse front. the CMU reads the time and date via the RTU system bus.

In the event of radio interference or DCF 77 interruption, the clock on the 560RTC02 will continue to use a high precision quartz clock. The internal condenser allows the

560RTC02 to continue to control the clock (approximately 150 hours), even when the station is turned off. Upon power-up, the RTU560 will have valid time immediately.

If the DCF 77 signal fails for more than 2.5 hours or the 560RTC02 is not synchronized, the alarm relay contacts close.

In addition to the minute pulse output for RTU560 synchronization, there is also a minute pulse output which is connected to the module via an optocoupler (MIN2).

The time, date and status can be read out every minute via the serial data output interface RS232.

ABB Air Control Unit (ACU)

The ABB Air Control Unit (ACU) is a high-performing and costefficient air flow controller for paint applications that is easy to integrate into new and existing installations. This extremely accurate and reliable unit controls air flow, enabling paint atomizers an incredibly fast response time, at an even lower working pressure than existing solutions.

Lightweight and compact, the ACU can be installed directly on the paint robot arm of both IRB 5400 and IRB 5500. As compared to the PPRU which is mounted inside the pneumatic cabinet on the IRB 5500, situated outside the spray booth. 

The new ACU design gives you faster response time plus stable and uniform air flow.

Optimize your paint process with the ACU to get access to all the benefits and significant paint- and energy savings.

Benefits include

Paint savings: 

− Minimized overspray

− Improved paint quality result

Energy savings:

− Lower air pressure

Productivity improvement:

− Reduced stop time

− Increased throughput

Paint savings with IPS

With the new ACU‘s millisecond response time you can now take full advantage of BB’s IPS system, designed to save paint. High acceleration painting robots combined with fast process regulation provide optimum use of paint material. In short, IPS reduces your www.cniacs.com cost to make you more profitable.

Quick and easy replacement 

The ACU replaces MAC-kit PPRU units on S4P, S4P+, and IRC5P paint robots. The replacement may require some adjustments for older generations. The ACU is a plug-andplay solution with pre-calibrated settings, easily fine-tuned or customized, ensuring an extremely accurate and stable overall performance.

Other benefits

− Mounted in the rear part of IRB 5500. near the atomizer

− EX-encapsulation

− Lightweight and compact, can be mounted on all robots

− Less internal pressure drop

− Built-in close loop regulation

− Modular plug-and-play design, easy and quick to install

− Supports ABB‘s StayOnTM and NoPatchTM concept

− Perfect for pattern control in Bell atomizers

− Replaces all previous obsolete control units

ABB PFVA401 Millmate Controller 400

The Millmate Controller 400 is designed to provide many features while being highly user friendly.

The MC 400 covers most mechanical arrangements. This means that the user only needs to follow step-by-step instructions to set up the controller and get the correct rolling force measurements.

. Predefined standard measurement modes .

. Built-in load cell table .

. Filtering times from 1 to 2000 ms .

. Easily configurable analogue/digital inputs/outputs

. Level Detectors

. Step Detectors

. Unit selection (N, kN, MN, kp, t, lb, T) .

. Self-diagnostic test system including sensor test

Data

External connections:

. Excitation current for load cell

. 2 or 4 analogue inputs for load cell signals.

.4 analogue outputs, voltage or current

.8 digital inputs for control www.cniacs.com signals

.8 digital outputs

. +.8 digital outputs .

. Ethernet connection for service and multiple control units .

.2 serial interfaces type RS-232 for external displays, controls, etc. .

. 1 serial interface type RS-485 for external display .

. High-speed Profibus (optional)

ABB Z401 PGC2000 Gas Chromatograph

Type of course and methodology

This course is delivered by an instructor, with approximately one-third of the course consisting of hands-on activities.

Trainee Profile

This training is intended for end-user analyser technicians, operators or engineers responsible for operating the PGC2000 process gas chromatograph.

Prerequisites

This course is an introductory level course designed for those who are new to this analyser system or need refresher training.

Course Objectives

Upon completion of this course, the participant will have a basic understanding of the fundamental operation of the PGC2000 process gas chromatograph.

The duration is 4 days.

www.cniacs.com Key Contents

– Basic Sample Systems

– Basic gas chromatography

– Analyser operation

– Controller section

– Oven section

Duration

The duration is 4 days.

ABB EIB Delta-Meter Plus Electricity Meters

EIB Delta-Meter Plus Electricity Meters

EIB Delta-Meters Plus are PTB-approved, electronic energy meters with an integrated ABB i-bus® EIB / KNX communication interface.

EIB Delta-Meters Plus are compact, reliable, immune to interference impulses and suitable for use in single-phase and polyphase voltage networks. As the meters have no mechanical moving parts, they can easily be snapped in any position onto DIN rails. The EIB communication interface enables remote reading of the meter data via the ABB i-bus® EIB for billing, energy optimisation, visualisation or installation monitoring purposes.

They can be universally employed for submetering applications in industrial installations, commercial buildings, offices, leisure complexes and private households.

Special features:

●   Precise measurement of energy consumption (kWh, kvarh with combination meter)

●   For 2-, 3- and 4-wire voltage networks with any load

●   Integrated EIB / KNX interface for remote reading of meter data

●   Network monitoring function: recording and display of up to 24 electrical measured variables

●   Automatic wiring check with an installation self-test

●   Easy to www.cniacs.com read LCD display, LED indicator for energy consumption

●   Direct connection up to 80 A

●   Transformer connection (/1A or /5 A) with transformer rated meter

●   Accuracy classes 1 or 2

●   Tariff meter with 4 tariffs

●   Fulfils standards IEC 61036/61268

●   Resistant to shocks and vibration, can be mounted in any position

●   System pro M design: can be snapped onto 35 mm DIN rail, sealable

ABB AZ100 series Zirconia oxygen analyzer

Introduction

The AZ100 Zirconia Oxygen Analyzer is a versatile system designed primarily for the OEM boiler and burner controls market.

The system is a low-temperature type designed to work in process temperatures up to 800 °C (1472 °F) and with a maximum sensor mounting flange temperature of 400 °C(752 °F).

The analyzer provides oxygen computation, with readout and retransmission, based on the probe mV output signal. The output signal (E mV) is Nernstian in form and follows the equation:

E (mv) = 0.0496T(log10 P0 / P1) ± CmV

Where:  T = Absolute temperature

P0 = Reference O2 partial pressure

P1 = Sample O2 partial pressure

C = Cell constant (mV zero offset)

0.0496 = Faraday’s gas constant

Probe design

The probe uses the proven and innovative ABB electrode and cell design technology which has been so reliable in other ABB zirconia probe designs.

The flexible probe design gives a range of intake tube lengths to suit all applications and an optional filter/flame arrester making it safe for use where groups IIB and IIC gases may occur in the process being measured. The probe has options of male thread NPT or BSPT mountings. As with all previous ABB designs of low temperature probes, the AZ100 probe is site-serviceable.

As the sensor housing is located on the outside of the duct wall, diffusion of reference air into the sensor housing is sufficient; thus eliminating the need for an air pump or instrument air supply.

The reference air diffuses into the housing through a porous membrane which restricts entry to air only and maintains the IP66 (NEMA 4X) protection.

Transmitter design

The transmitter has, as standard, high/low alarm relays and a single linear or logarithmic isolated retransmission. Display features include %O2. cell temperature, heater control output, cell mV, alarm set points, calibration sequence diagnostics and output settings.

At system startup the transmitter controls the level of power to the mains-powered heater within the probe to eliminate the risk of thermal shock to the sensor.

Based on the proven 4600 Series of transmitters, the AZ100 transmitters are environmentally protected to NEMA 4X (IP65)*, and meet the requirements EN61326 for industrial locations.

The AZ100 transmitters have a green, backlit LCD display and four tactile membrane switches for operation and programming. The measured value display is a 5-digit, 7-segment LCD, while the information display is a 16-character, single line, dot-matrix.

The information display can be user-programmed for display in English, French, German or Spanish.

ABB Trip circuit supervision relay TCS

Continuous supervision of complete trip circuit independent of circuit breaker position

The supervision relay type TCS is intended for a continuous supervision of circuit breaker trip circuit and gives an alarm for loss of auxiliary supply, faults on the trip coil or its wires independent of the breaker position, faults on the breaker auxiliary contacts and faults in the supervision relay. The trip circuit supervision is a crucial requirements as its failure can cause disconnect of possible network fault and eventually have to be cleared by another upstream protection.

In normal condition, the indicator LE D glows green and output relays are in picked-up condition. In the event of a fault, the supervision relay operates (drops-off)www.cniacs.com after a delay of 0.6 sec and the indicator LED turns red.

TCS relay product range

• Rated voltage: 24V DC, 30V DC, 48V DC, 100-125V AC/DC, 220-250V AC/DC

• Contact configuration: 1NO+1NC+2C/O

Main benefits

• Highly reliable

• Personnel as well as power system safety

• Easy site installation

Main features

• Continuous supervision of trip circuit independent of the circuit breaker position

• Galvanic isolation between auxiliary supply and supervision circuit

• Delayed operation to avoid spurious signals during circuit breaker operation

• Enables use in sensitive or high resistance circuits

• Extremely low burden on auxiliary source

• Complete range of rated voltages either AC/DC

Features

• Continuous supervision of trip circuit independent of the circuit breaker position

• Extremely low burden on auxiliary source

•  Complete range of rated AC / DC voltage

•  Operation indication for trip circuit healthy and unhealthy

•  Low-level measuring current enables application of relay for high burden circuits

•  Delayed operation to avoid spurious signals during circuit breaker operation

•  Galvanic isolation between auxiliary supply and supervision circuit

ABB Ethernet Communications offers managed and unmanaged switches for Ethernet communications

Ethernet Communications

Innovative Products for Ethernet Data Transfer in SCADA Applications

Innovative products for Ethernet data transmission in applications

Ethernet communication Managed and unmanaged switches for Ethernet communication are available. the DSL technology and the tunnelling capability of the serial protocols make it possible to switch directly from conventional serial Voice Frequency Telegram (VFT) transmission to Ethernet communication while retaining the existing copper wires without having to adapt the serial terminals, e.g. for remote control technology.

Features such as Rapid Spanning Tree Protocol (RSTP), bypass circuits such as those found in UMTS or Tetra modems, and the use of optical communication www.cniacs.com lines are also available for increased usability.

Managed Ethernet Switches

Highlights

– Connects over copper wires:

– DSL coverage of up to 20 km based on (S(H)DSL)

– DSL connection via 2-wire at speeds from 192 to 11400 kbps

– Automatic speed adjustment according to line quality

– Compatible with other S(H)DSL modems via IEEE EFM (IEEE 802.3)

– DSL transmission quality (signal vs. noise level) monitoring/messaging

– 560NMS24 can automatically connect lines in case of power failure

– Optical connection:

– SFF slot for insertion of SFP modules

– Supports SFP modules for multimode and singlemode fibre cables

– Transmission speed of 100 Mbps

– Coverage of up to 40 km, depending on the SFP module

– Transmission of serial protocols on up to two serial interfaces

– Point-to-point, split-wire and signal sampling

– Each interface can have a different data rate

– 4-port 10/100 BaseT switch for connecting devices (VLAN assignable)

– Network topologies supported: point-to-point, point-to-multipoint and ring

– Redundant transport routing over copper, optical fibre and bypass circuits to external TCP/IP modems (e.g. UMTS or Tetra)

– Fast Spanning Tree Protocol, link aggregation, VLANs, QoS, port mirroring, static and dynamic routing (RIP)

– Repeater functionality

– Transmission of system events from the switch via IEC 60870-5-101/104

– Configurable alarm relays

– 2 binary inputs/outputs per serial interface (requires external circuitry)

– Configuration via RS232. Simple Network Management Protocol (SNMP), Telnet, Secure Shell (SSH), Web interface, optional login via Radius server

– Easy device replacement via configuration flash drive

– Suitable for harsh environmental conditions:

– High Electromagnetic Compatibility (EMC) safety.

– High electromagnetic compatibility (EMC) safety -25… + 70 °C

– Integrated overvoltage protection

– No fans or moving parts

– Supply voltage: 24…. . 60 VDC

ABB IRB 1200 One of the new generation of 6-axis industrial robots

The IRB 1200 is one of the latest generation of 6-axis industrial robots from ABB Robotics with a payload of 5 to 7kg.

It is designed for manufacturing industries that use robot-based flexible automation, such as the 3C industry.

The robot’s open architecture makes it particularly suitable for flexible use and allows extensive communication with external systems.

IRB 1200 Type A

Type A – Axis Calibration

The difference between the IRB 1200 and the IRB 1200 Type A is that the Type A uses axis calibration. Each axis has a bushing on which the calibration tool is mounted.

Therefore, the castings of the IRB 1200 and IRB 1200 A models are different.

How do I know the type of robot?

The type label on the robot base indicates whether the robot is axis calibrated or not.

These robots are named IRB 1200 A models.

Robots that are not axis calibrated are simply named IRB 1200 (no type indicated).

IRB 1200 Type B

Type B – SafeMove 2

The IRB 1200 Type B differs from the other www.cniacs.com IRB 1200 versions in that

Type B supports SafeMove 2.

Therefore, the following components differ from the other versions:

– Base

1.1.1 Construction

Continued

– Drive unit, shaft 2. shaft 3. shaft 5 and shaft 6

– Motor with pulley, shaft 4 and shaft 5

– Robot cable harness

– Battery pack

– SMB unit (replaces EIB unit)

ABB New VD4 Medium Voltage Vacuum Circuit Breaker

Overview of the new VD4 Medium Voltage Circuit Breaker

The new VD4 Medium Voltage Circuit Breaker is the perfect combination of vacuum interrupter design and manufacturing technology with resin-embedded pole plates and technical excellence in circuit breaker design, engineering and production.

The VD4 medium voltage circuit breaker uses vacuum interrupters embedded in resin pole plates.

Embedding the interrupters in resin poles makes the circuit breaker poles particularly robust and protects the interrupters from shock, dust build-up and moisture.

A vacuum interrupter consists of a contact and an interrupting chamber.

Vacuum interrupters Vacuum circuit breakers do not require an interrupting and insulating medium. In fact, the interrupter chamber contains no ionisable material.

In any case, the arc generated when the contacts separate consists entirely of melted and vapourised contact material.

The arc is supported by external energy until the current disappears near its natural zero point.

At this point, the load density decreases rapidly and the metal vapour condenses rapidly, leading to an extremely rapid recovery of the dielectric properties.

The vacuum interrupter thus regains its insulating capacity and its ability to withstand transient recovery voltages, and the arc is finally extinguished.

Due to the high dielectric strength achieved in a vacuum even at short distances, circuit interruption is guaranteed when the contacts separate a few milliseconds before the current passes through the natural zero point.

The special geometry of the contacts and the materials used, as well as the limited duration of the arc and the low voltage

guarantees minimum wear and a long service life of the contacts. In addition, the vacuum prevents oxidation and contamination of the contacts.

Structure

The operating mechanism and the magnetic poles are fixed to a metal frame which also serves as a support for the fixed circuit breakers.

The compact construction ensures robustness and mechanical reliability.

In addition to isolating contacts for connecting auxiliary circuits and flexible cables with plugs, the

The tractable circuit breakers are also equipped with a www.cniacs.com bracket trolley for putting them into or taking them out of the switchgear or enclosure with the door closed.

– Vacuum interrupter technology

– Vacuum contacts protect against oxidation and contamination

– Vacuum interrupters embedded in resin poles

– The interrupters are protected against vibration, dust and humidity.

– Poles sealed for life

– Operation in different climatic conditions

– Limited switching energy

– Energy storage operating mechanism with anti-pumping device as standard

– Simple customisation with a full range of accessories

– Fixed and withdrawable

– Compact dimensions

– Compact dimensions Robust and reliable

– Limited maintenance

– Doors closed when circuit breakers are racked in and out

– Special locks on the operating mechanism and forklift truck prevent incorrect and dangerous operation

– High environmental compatibility