Specifications

Inputs per Module: 8. 16 or 32

Classic

Isolation: 1500 VDC channel-to-backplane

1500 VDC group-to-group

Input Voltage:

Range Setting

12/24V range

48V range

110V range

220VAC range

Operating Range

11 – 30 volts

40 – 56 volts

79 – 132 volts

164 – 240 volts

*NOTE: 220V range is AC only

Input Current: AC: 2.1—3.6 mA

DC: 2.5—4.3 mA

Operating Characteristics for Typical Input:

AC Voltage Input:

Turn ON Time:    4.0mS

Turn OFF Time:    15.0mS

DC Voltage Input:

Turn ON Time:    1.0mS

Turn OFF Time:    15.0mS

Connector: 2500-40F Removable Connector (sold

separately)

Wire Gauge: 14-22 AWG

Backplane Power: 3.6 Watts max.

Module Size:  Single-wide

Operating Temperature: 0° to 60°C

(32° to 140°F)

Storage Temperature:  -40° to 85°C

(-40° to 185°F)

Relative Humidity:  5% to 95%

(non-condensing)

Shipping Weight:  1.5lb (0.68 Kg)

Voltage Range Selection Jumpers

The 2589-B will handle a wide range of AC and DC signals,

and has incorporated the ability to select either 12V/24V, 48V,

110V, or 220V on a per channel basis using jumper selection.

The selections are made individually for each of the 32

channels using jumpers. However, the same voltage range

must be selected for all channels in the same group. The

operating ranges are as follows:

Range Setting

12/24V range

48V range

110V range

220VAC range

Operating Range

11 – 30 volts

40 – 56 volts

79 – 132 volts

164 – 240 volts

* NOTE: 220V range is AC only