Specifications

Outputs: 16

Logon: 16Y/16X or 16Y

Isolation:

1500 VDC channel-to-channel

1500 VDC channel-to-backplane

Blown fuse reporting per channel:

Reported to the PLC as an X input (jumper selectable)

Output voltage: 20 to 132 VAC

Output source current per circuit: 2.0 A max

“OFF” state leakage: 1mA max @ 25°C

Turn ON or OFF time: 1/2 AC cycle

Non-repetitive surge current: 80 Amps for 1 cycle

Total module output current: 32 Amps

Connector: Removable 40 Pin Connector

(ordered separately CTI Part # 2500-40F)

Wire gauge: 14 to 22 AWG

Backplane power: 2.5 watts max

Module size: Single wide

Fuses: 16. 3 Amp, 250V Type Littlefuse #2173.15

or Bussman GMA #GMA-3A or CTI Part Number

#80-65(Field Replaceable).

Shipping Weight:  1.5 lbs (0.68Kg)

Additional Product Information:

On CTI’s Website you will find links to the 2500 Series

Std Environmental Specifications and the UL Agency

Certificates of Compliance