Specifications

Outputs: 16

Output voltage: 20 to 132 VAC

Output source current per circuit:  2.0A max

Minimum current: 40 mA per circuit

Non-repetitive surge current: 80 Amps (1 cycle)

“OFF” state leakage: 1 mA maximum @ 25°C

Turn ON or OFF time: 1 AC cycle

Total module output current: 32 Amps max

Fuses: 16. 3 Amp, 250 V, Type Littlefuse

#2173.15. Bussman GMA# GMA-3A,

CTI Part #80-65 (field replaceable)

Specifications 2591-EF

Outputs: 16

Output voltage: 11 to 146 VDC

Output source current per circuit:  1.5A max

Maximum surge current:3 Amps for 15 seconds

“ON” state voltage drop:0.3 V @ 1.5 Amps

“OFF” state leakage current:125 µA @ 146 VDC

Turn ON time:0.5 mSec (nominal)

Turn OFF time: 1.5 mSec (nominal)

Total module output current: 24 Amps max

Fuses: 16. 1.6 Amp, 250 V, Schurter #034.2518

CTI Part #80-79 (field replaceable)

Specifications Common to Both

Isolation: 1500 VDC channel-to-channel

1500 VDC channel-to-backplane

Connector: Removable

Wire gauge:14-22 AWG

Backplane power:2.5 watts max

Module size:  Double wide

Blown fuse indication: Front panel LED (per channel)

Blown fuse reporting:

Reported to PLC as X input per channel (jumper selectable)

Operating temperature: 0° to 60°C (32° to 140°F)

Storage temperature:-40° to 85°C (-40° to 185°F)

Humidity, relative:5% to 95% (non-condensing)

Agency approvals:  UL, UL Canada, FM (Class, Div 2)