Specifications

Inputs per module: 16 (2 outputs per common)

Isolation:

500 VDC group-to-group

1500 VDC channel-to-backplane

1500 VDC channel-to-backplane

Output Drive Capabilities:

High (VOH) (minimum) = 4.5 V @ 500 μA

Low (VOL) (maximum) = 0.4 V @ 30 mA

Rise/Fall Time = 1 μSec

Outputs are true “low” when energized

Sink Current: (maximum per output) 50 mA

PLC Reporting: X or WX (jumper selectable)

Wire gauge: 14-22 AWG removable connectors

Backplane power: 2 Watts max

Module size: Single-wide

Blown fuse indication: Front panel LED

Shipping weight:1 lb. (0.45 Kg)

Additional Product Information:

On CTI’s Website you find will links to the 2500

Series  Std Environmental Specifications and the UL

Agency Certificates of Compliance .