Specifications

Outputs per Module: 8

Logon: 8Y

Isolation:

2100 VDC channel-to-backplane

3000 VDC group-to-group

Output Voltage: 11 VDC to 125 VDC

Output Source Current per Circuit:

2.0 Amps max., 1 mA min.

Total Module Output Current:

16 Amps max. from 0° to 60°C

Maximum Surge Current: 3 Amps for 15 Sec

“ON” State Voltage Drop: 0.5V @ 1.0 Amp

“OFF” State Leakage Current: <20µA

Turn  On Time: 1 mSec (nominal)

Turn  Off Time: 3 mSec (nominal)

Fuses:  8. 2.5 amp, 250V,

Type: Littlefuse #21602.5.

Bussman GDA-2.5 (Field replaceable)

Connector: Removable 40 Pin Connector

(ordered separately CTI Part # 2500-40F)

Wire Gauge: 14 – 22 AWG

Backplane Power: 1.0 Watts max.

Module Size:  Single-wide

Shipping Weight: 1.5 lb. (0.68 Kg)

Additional Product Information:

On CTI’s Website you will find links to the 2500

Series  Std Environmental Specifications and the UL

Agency Certificates of Compliance.